Whirlpool W4GH6 Troubleshoot the Defrost System, Defrost Control Setting, Defrost Test Cycle Time

Models: W4GH6

1 20
Download 20 pages 46.03 Kb
Page 14
Image 14
Troubleshoot the Defrost System

2.Remove the heater compartment access panel.

3.Adjust the time period between defrost cycles by placing the defrost time plug in the proper position. See “Defrost Control Board.”

For 30-minute intervals between defrost cycles, connect the Defrost Time Setting Plug to the pins corresponding to 30.

For 60-minute intervals between defrost cycles, connect the Defrost Time Setting Plug to the pins corresponding to 60 (this setting is the factory preset setting).

For 90-minute intervals between defrost cycles, connect the Defrost Time Setting Plug to the pins corresponding to 90.

4.Replace the heater compartment access panel.

5.Reconnect power.

Troubleshoot the Defrost System

Defrost Control SettingWARNING

Electrical Shock Hazard

Disconnect power before servicing.

Replace all parts and panels before operating.

Failure to do so can result in death or electrical shock.

The defrost control is equipped with a set of pins (labeled TEST on control circuit board) to aid in troubleshooting the defrost system. Connecting the test pins speeds up the defrost cycle time by a factor of 256.

1.Disconnect power.

2.Remove control box cover.

3.Connect the test pins on the defrost control using a test jumper wire.

NOTE: If the outdoor temperature is above 32°F, connect the defrost sensor terminals using a test jumper wire. See “Defrost Control Board” in the “Adjust Defrost System” section.

4.Replace control box cover.

5.Reconnect power.

6.Start system in heating operation.

7.Time the defrost test cycle as determined by the chart. After the corresponding defrost cycle time from the chart below has elapsed, the reversing valve should shift to defrost mode and the outdoor fan should stop. After 2 seconds of defrost operation, the reversing valve should shift back to heating operation and the outdoor fan should start.

NOTE: If this procedure is not observed, check the reversing valve solenoid for correct operation by measuring temperatures and pressures under heating and cooling modes. If the reversing valve solenoid operates correctly then replace the defrost control board. See “Sequence of Operation.”

Defrost Control Setting

Defrost Test Cycle Time

 

 

T1 - 30 minutes

7 seconds

 

 

T2 - 60 minutes

14 seconds

 

 

T3 - 90 minutes

21 seconds

 

 

8.If an adjustment is required, see “Adjust Time Between Defrost Cycles” in the “Adjust Defrost System” section.

9.Disconnect power.

10.Remove control box cover.

11.Remove jumper from test pins and jumper from defrost sensor terminals, if used.

12.Replace control box cover.

13.Reconnect power.

14

Page 14
Image 14
Whirlpool W4GH6 installation instructions Troubleshoot the Defrost System, Defrost Control Setting, Defrost Test Cycle Time