Whirlpool W4GH6 VAC Power Wiring, Thermostat Demand Wiring, Flash Codes, LED Status

Models: W4GH6

1 20
Download 20 pages 46.03 Kb
Page 16
Image 16
24 VAC Power Wiring

Flash Codes

LED Status

Fault Description

Troubleshooting Information

 

 

 

 

Alert (Yellow) Flash Code 3

Short Cycling: Compressor is

Thermostat demand signal is intermittent.

 

running only briefly.

Time delay relay or control board is defective.

 

 

 

 

If high pressure switch is present, go to Flash Code

 

 

 

2 information.

 

 

If low pressure switch is present, go to Flash Code

 

 

 

1 information.

 

 

 

 

Alert (Yellow) Flash Code 4

Locked Rotor

Run capacitor has failed.

 

 

Low line voltage (contact utility if voltage at disconnect is low).

 

 

Excessive liquid refrigerant in the compressor.

 

 

Compressor bearings are seized.

 

 

 

 

Alert (Yellow) Flash Code 5

Open circuit

Outdoor unit power disconnect is open.

 

 

Compressor circuit breaker or fuse(s) is open.

 

 

Compressor contactor has failed to open.

 

 

High pressure switch is open and requires manual reset.

 

 

Open circuit in the compressor supply wiring or connections.

 

 

Unusually long compressor protector reset time due to the

 

 

 

extreme ambient temperature.

 

 

Compressor windings are damaged.

 

 

 

 

Alert (Yellow) Flash Code 6

Open Start Circuit: Current

Run capacitor has failed.

 

only in run circuit.

Open circuit in the compressor start wiring or connections.

 

 

Compressor start winding is damaged.

Alert (Yellow) Flash Code 7

NOTE: This code will flash within 5 minutes of power interruption until the 5 minute short cycle timer has elapsed. Allow at least 5 minutes of run time before confirming this code.

Open Run Circuit: Current

Open circuit in the compressor run wiring or connections.

only in start circuit

Compressor run winding is damaged.

 

 

Alert (Yellow) Flash Code 8

Welded Contactor:

Compressor contactor has failed to close.

 

 

Compressor always runs.

Thermostat demand signal not connected to the module.

 

 

 

 

 

 

 

 

 

Alert (Yellow) Flash Code 9

Low Voltage: Control circuit

Control circuit transformer is overloaded.

 

 

less than 17 VAC

Low line voltage (contact utility if voltage at disconnect is low).

 

 

 

 

 

 

 

 

 

24 VAC Power Wiring

 

 

Thermostat Demand Wiring

 

 

 

 

 

The diagnostic module requires a constant nominal 24 VAC power supply. The wiring to the module’s R and C terminals must be directly from the indoor unit or thermostat. The module cannot be powered by R and C terminals on the defrost board without experiencing nuisance alerts.

The diagnostic module requires a thermostat demand signal to operate properly. The thermostat demand signal input, labeled Y on the module, should always be connected to the compressor contactor coil so that when the coil is energized, the demand signal input is 24 VAC. When the coil is not energized, the demand signal input should be less than 0.5 VAC.