White Rodgers 1F94W-71 manual Automatic Changeover

Models: 1F94W-71

1 40
Download 40 pages 23.34 Kb
Page 13
Image 13

small screwdriver to move the switch to the ON position (see figure at right). Leave the battery out of the thermostat for at least two minutes, to allow the thermostat to reset itself. DO NOT MOVE OPTION SWITCHES #1 OR #2, as this may affect thermostat operation. [Option switch #3 enables/dis- ables keypad lockout (see TOTAL KEY- PAD LOCKOUT)]. Replace the battery, re- program the thermostat, if necessary, put the thermostat back on the wall, and restore 24 VAC power. To set the thermostat for automatic changeover after programming,

press

SYSTEM

to set the thermostat to AUTO

HEAT/EMER/OFF/

 

COOL/AUTO

 

(the setpoint temperature display is blank in the AUTO mode). The system will now automatically switch between heating and cooling, depending on the actual room tem- perature.

Automatic Changeover

ON

1 2 3 4

Switch #1 set at installation (DO NOT CHANGE) Switch #2 set at installation (DO NOT CHANGE) Switch #3 (see TOTAL KEYPAD LOCKOUT)

Switch #4 ON

In the AUTO mode, the thermostat will not allow the temperature separation between the highest heat setting and the lowest cool setting to be less than 1°F. For example, if the highest heat setting is 76°F, the lowest cool setting cannot be below 77°F (see diagram below).

79

COOLING TEMPERATURES

78

 

 

77

 

DEAD BAND 1°F

76

 

75

HEATING TEMPERATURES

74

 

 

73

 

 

13

Page 13
Image 13
White Rodgers 1F94W-71 manual Automatic Changeover