SECTION X - MAXITROL VALVE ADJUSTMENTS

SECTION X - MAXITROL VALVE ADJUSTMENTS

AND PRELIMINARY CIRCUIT ANALYSIS

MR212 Valve

M411, 511, 611 Valve

High Fire Manifold Adjustments

1.Disconnect wires from amplifier terminal #4 (Series 14), or #2 and #4 (Series 44). This causes the valve to call for continuous high fire.

2.Remove seal cap (A) and turn regulator pressure adjusting screw to obtain desired manifold pressure. (Clockwise rotation increases pressure.)

3.Reconnect the wires to amplifier terminal #4 (Series 14), or #2 and #4 (Series 44).

NOTE: If low bypass is on maximum, the desired high fire outlet pressure may not be achieved.

Low Fire or Bypass Adjustments

1.Disconnect wire from amplifier terminal #8. This causes valve to call for continuous low fire.

2.Remove cap (B) and loosen lock screw (C). Turn (D) to desired low fire adjustment. (Clockwise rotation reduces minimum flow rate.)

3.Tighten screw (C), replace cap (B) and reconnect wire to amplifier to terminal #8.

High Fire Manifold Adjustments

1.Disconnect wires from amplifier terminal #4 (Series 14), or #2 and #4 (Series 44). This causes the valve to call for continuous high fire.

2.Adjust the pressure regulator to obtain the rating plate manifold pressure.

3.Reconnect the wires to amplifier terminal #4 (Series 14) or #2 and #4 (Series 44).

Low Fire or Bypass Adjustments

1.Disconnect wire from amplifier terminal #8. This causes the valve to call for continuous low fire.

2.Remove cap (A) and turn adjusting screw (B) to desired low fire adjustment. (Clockwise rotation reduces minimum flow rate.)

3.Replace cap (A) and reconnect wire to amplifier terminal #8.