Step 6: Performing Checks Prior to Initial Start-Up

Before testing your installation, ensure these conditions are met:

Chassis and AC grounds are properly installed.

AC input connections and AC output connections are wired correctly on the terminal block and not reversed.

Positive (+) battery cable is connected to the positive (+) battery terminal through the DC fuse and disconnect switch or DC circuit breaker.

Negative (–) battery cable is connected to the negative (–) battery terminal.

Battery voltage is within the proper range for this unit (11–15 volts DC).

DC disconnect switch or breaker is turned off.

AC input and output breakers are turned off.

All connections are tight.

Installing the Inverter/Charger

This guide for use by qualified installers only.

975-0527-01-01