Cable Installation
152602 2–5
Cable Installation

Wire Gauge and Torque Specifications

The following torque specifications are to be used on all electrical
interfaces made during installation of the GT100E MS Combiner Box.

Wire Gauge Requirements for the GT100E MS Combiner Box

One or multiple wires up to 300 mm2 can be connected to the GT100E
MS Combiner box. Follow local Electrical codes to determine the correct
wire gauge.

Torque Specifications for the GT100E MS Combiner Box

M10 Bolt 40.0Nm
M12 Bolt 54.0Nm
M16 Bolt 132.0Nm
CAUTION
All wiring methods and wire gauges shall be in accordance with Local Electrical
Code. Take care to keep the wire bundles away from any sharp edges which may
damage wire insulation over time.