Cable Installation

Cable Installation

CAUTION

All wiring methods and wire gauges shall be in accordance with Local Electrical Code. Take care to keep the wire bundles away from any sharp edges which may damage wire insulation over time.

Wire Gauge and Torque Specifications

The following torque specifications are to be used on all electrical interfaces made during installation of the GT100E MS Combiner Box.

Wire Gauge Requirements for the GT100E MS Combiner Box

One or multiple wires up to 300 mm2 can be connected to the GT100E MS Combiner box. Follow local Electrical codes to determine the correct wire gauge.

Torque Specifications for the GT100E MS Combiner Box

M10 Bolt

40.0Nm

M12 Bolt

54.0Nm

M16 Bolt

132.0Nm

152602

2–5

Page 21
Image 21