SECTION 4
OPERATION
|
| User |
| Factory | Password | |
Parameter | Description | Settable | Resolution | Default | ||
|
| Range |
| Setting | Protected | |
|
|
|
|
|
| |
Volts Max | Maximum Allowable | 0.1 V | 228.8 | * | ||
Utility Voltage | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
Cycle Max | High Line Voltage | 1 Cycle | 115 | * | ||
Timer, Cycles | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
Volts Min | Minimum Allowable | 0.1 V | 183.0 | * | ||
Utility Voltage | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
Cycles Min | Low Line Voltage | 1 Cycle | 115 | * | ||
Timer, Cycles | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
Freq Max Delta | High Line Frequency | 0.1 Hz | 0.5 | * | ||
Level | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
Freq Min Delta | Low Line Frequency | 0.1 Hz | 0.5 | * | ||
Level | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
| Maximum Allowable |
|
|
|
| |
Freq Max Delay | Time Response To A | 1 Cycle | 6 | * | ||
Utility High Frequency | ||||||
|
|
|
|
| ||
| Excursion |
|
|
|
| |
|
|
|
|
|
| |
| Maximum Allowable |
|
|
|
| |
Freq Min Delay | Time Response To A | 1 Cycle | 6 | * | ||
Utility Low Frequency | ||||||
|
|
|
|
| ||
| Excursion |
|
|
|
| |
|
|
|
|
|
| |
Line Fault Reset Delay | Line Fault Reset Delay | 1 Second | 300 | * | ||
Time | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
PV Start V | PV Wake Up Voltage | 0.1 V | 380 |
| ||
|
|
|
|
|
| |
PV Decision W | Maximum Start Up | 0.1 W | 1880 |
| ||
Power |
| |||||
|
|
|
|
| ||
|
|
|
|
|
| |
PV_Start_Time | PV Wake Up Time | 1 Second | 300 |
| ||
|
|
|
|
|
| |
PV_Sleep_Time | PV Sleep Time | 1 Second | 300 |
| ||
|
|
|
|
|
| |
Gnd Current Max | Maximum Earth Fault | 0.1 A | 10 |
| ||
Current Limit |
| |||||
|
|
|
|
| ||
|
|
|
|
|
|
DOCUMENT: 151315 | ||
| Operation and Maintenance Manual |
|
Copyright 2003, Xantrex Technology