SECTION 5
TROUBLESHOOTING
GENERAL
In the event of a fault, the
In general, the operator should respond to any
1.The source of the fault should be sought by referring to the following chart.
2.Rectify the fault condition and attempt to clear the fault by cycling the on/off switch.
3.If the problem cannot be corrected, note and write down the fault code and description, then contact your Xantrex Technology distributor for assistance or service.
FAULT CONDITIONS
LCD Fault Annunciation
The LCD interface reports fault conditions on Line 2 and 3. The fault code number will follow a text description. The fault description will remain displayed until the fault has been corrected and cleared. Each fault is described on the following page.
Fault Clearing
Faults may be cleared automatically by the
Latching faults must be cleared manually by the system operator. Once the cause of the fault condition has been corrected, the fault may be cleared with the on/off switch. First turn the switch to the off position and then back to the on position in order to reset the inverter. If a fault is sustained, the inverter will not reset, and will continue to report the fault. If the fault has been corrected, the LCD will return to the normal display, and the
LCD Display and On/Off Switch
DOCUMENT: 151315PV-30208 Photovoltaic Inverter5-1
Operation and Maintenance Manual