SECTION 1

PRODUCT DESCRIPTION

SPECIFICATIONS

The PV-30208 has been designed for photovoltaic power systems, which operate within the following specifications. Application of the PV-30208 in a manner inconsistent with these specifications may cause damage to the PV-30208 and other system components, and is a violation of the terms of the warranty.

Nominal AC Line Voltage

208 VAC, +10% -12%

 

 

Maximum AC Line Current

94 ARMS (at low line voltage)

 

 

Nominal Line Frequency

60 Hz, +0.5 Hz -0.7 Hz

 

 

Continuous AC Output Power

30.0 KW @ 208 VAC 3 Phase

 

 

PV MaximumVoltage

600 VDC

Peak Power Tracking Window

330*-600 VDC

 

 

PV Minimum Peak Power Tracking Voltage

330

 

 

PV Maximum Current

100 ADC

 

 

PV Maximum Array Short Circuit Current

138 ADC

 

 

PV Configuration

Monopolar negative grounded, or bi-polar

neutral ground

 

Operating Temperature

**-20 to 50° C

 

 

Storage Temperature

-40 to 50° C

 

 

Maximum Ambient Temperature Rating

50° C

 

 

Relative Humidity

To 95%, Non-condensing

 

 

Elevation

Derated above 6,600 feet

 

 

Dimensions (in inches)

54.5 X 35.6 X 19

 

 

Weight

Approx. 260 lbs.

 

 

Enclosure Type

NEMA 3R

 

 

UL Listing File

File-E199356

 

 

*Dependent on actual AC line voltage. Refer to Section 4 for detail on the minimum power tracking voltage.

**If ambient temperature is between -20 to 0° C, the unit must be powered up in standby for at least one hour prior to going on-line.

EQUIPMENT SYMBOL

Chassis ground – Customer supplied system ground connection point. This symbol may be found near a stud within the main enclosure. It is provided as a location to bond the electrical system equipment ground.

DOCUMENT: 151315PV-30208 Photovoltaic Inverter1-3

Operation and Maintenance Manual

Copyright 2003, Xantrex Technology Inc.

Page 5