Specifications and Characteristics
A–2 TM-XDOP-01XN
Electrical Specifications—Summary

Table A-1

Specifications for 6000 Watt units (10V to 60V Models)

Models 10-600 20-300 30-200 40-150 60-100
Output Ratings:
Output Voltage a
Output Current b
Output Power
a. Minimum output voltage is <0.3% of rated voltage at zero output setting.
b. Minimum output current is <0.2% of rated current at zero output setting when measured with rated load resistance.
0–10 V
0–600 A
6000 W
0–20 V
0–300 A
6000 W
0–30 V
0–200 A
6000 W
0–40 V
0–150 A
6000 W
0–60 V
0–100 A
6000 W
Line Regulation: c
Voltage (0.01% of Vmax)
Current (0.05% of Imax)
c. For input voltage variation over the AC input voltage range, with constant rated load.
1mV
300mA 2mV
150mA 3mV
100mA 4mV
75mA 6mV
50mA
Load Regulation: d
Voltage (0.05% of Vmax + 5mV)
Current (0.1% of Imax + 20 mA)
d. For 0–100% load variation, with constant nominal line voltage.
10mV
620mA 15mV
320mA 20mV
220mA 25mV
170mA 35mV
120mA
Meter Accuracy:
Voltage (0.15% of Vmax)
Current (0.5% of Imax) 15mV
3A 30mV
1.5A 45mV
1.0A 60mV
750mA 90mV
500mA
Output Noise (0–20 MHz):
Voltage (p–p) 75mV 75mV 75mV 75 mV 100mV
Output Ripple (rms):
Voltage
Current e
e. Current mode noise is measured from 10% to 100% of rated output voltage, full current, unit in CC mode.
10mV
3100 mA 10mV
1600 mA 12mV
1000 mA 15mV
750mA 15mV
450mA
OVP Adjustment Range:
(0% to 103% of Vmax) 0–10.3 V 0–20.6 V 0–30.9 V 0–41.2 V 0–61.8 V
Efficiency: f
f. Typical efficiency at nominal input voltage and full output power.
0.85 0.87 0.87 0.87 0.89
Drift (30 minutes): g
Voltage (0.04% of Vmax)
Current (0.6% of Imax)
g. Maximum drift over 30 minutes with constant line, load, and temperature, after power on.
4mV
3600 mA 8mV
1800 mA 12mV
1200 mA 16mV
900mA 24mV
600mA
Drift (8 hours): h
Voltage (0.02% of Vmax)
Current (0.04% of Imax)
h. Maximum drift over 8 hours with constant line, load, and temperature, after 30 minute warm-up.
2mV
240mA 4mV
120mA 6mV
80mA 8mV
60mA 12mV
40mA
Temperature Coefficient: i
Voltage (0.04% of Vmax/°C)
Current (0.06% of Imax/°C)
i. Change in output per °C change in ambient temperature, with constant line and load.
4mV
360mA 8mV
180mA 12mV
120mA 16mV
90mA 24mV
60mA