Electrical Specifications—Summary
TM-XDOP-01XN A–3
)
Table A-2Specifications for 6000 Watt units (80V to 600V Models)
Models 80–75 100–60 150–40 300–20 600–10
Output Ratings:
Output Voltage a
Output Current b
Output Power
a. Minimum output voltage is <0.3% of rated voltage at zero output setting.
b. Minimum output current is <0.2% of rated current at zero output setting when measured with rated load resistance.
0–80 V
0–75 A
6000 W
0–100 V
0–60 A
6000 W
0–150 V
0–40 A
6000 W
0–300 V
0–20 A
6000 W
0–600 V
0–10 A
6000 W
Line Regulation: c
Voltage (0.01% of Vmax)
Current (0.05% of Imax)
c. For input voltage variation over the AC input voltage range, with constant rated load.
8mV
37.5 mA 10 mV
30 mA 15 mV
20mA 30 mV
10mA 60 mV
5mA
Load Regulation: d
Voltage (0.05% of Vmax + 5mV)
Current (0.1% of Imax + 20 mA)
d. For 0–100% load variation, with constant nominal line voltage.
45 mV
95 mA 55mV
80 mA 80mV
60mA 155 mV
40mA 305 mV
30mA
Meter Accuracy:
Voltage (0.15% of Vmax)
Current (0.5% of Imax) 120 mV
375 mA 150 mV
300 mA 225 mV
200mA 450mV
100mA 900mV
50mA
Output Noise (0–20 MHz):
Voltage (p–p) 100 mV 100 mV 150 mV 250mV 350mV
Output Ripple (rms):
Voltage
Current e
e. Current mode noise is measured from 10% to 100% of rated output voltage, full current, unit in CC mode.
15 mV
320 mA 20 mV
230 mA 20 mV
120mA 30mV
50mA 80 mV
25mA
OVP Adjustment Range:
(0% to 103% of Vmax) 0–82.4 V 0–103V 0–154.5 V 0–309 V 0–618 V
Efficiency: f
f. Typical efficiency at nominal input voltage and full output power.
0.89 0.90 0.90 0.91 0.91
Drift (30 minutes): g
Voltage (0.04% of Vmax)
Current (0.6% of Imax)
g. Maximum drift over 30 minutes with constant line, load, and temperature, after power on.
32 mV
450 mA 40 mV
360 mA 60 mV
240mA 120mV
120mA 240mV
60mA
Drift (8 hours): h
Voltage (0.02% of Vmax)
Current (0.04% of Imax)
h. Maximum drift over 8 hours with constant line, load, and temperature, after 30 minute warm-up.
16 mV
30 mA 20mV
24 mA 30mV
16mA 60 mV
8mA 120mV
4mA
Temperature Coefficient: i
Voltage (0.04% of Vmax/°C)
Current (0.06% of Imax/°C)
i. Change in output per °C change in ambient temperature, with constant line and load.
32 mV
45 mA 40mV
36 mA 60mV
24mA 120 mV
12mA 240 mV
6mA
TM-XDOP-01XN.book Page 3 Monday, July 17, 2006 11:19 AM