Current Sharing
Overview
Release 1.0 21
Current Share
Configuration
Units are programmed in a mode such that it is already in current sharing mode on
power up. This feature is not user-modifiable. Please c ontact the manufacturer for
assistance if you wish to change this.
Most configurable settings available on a m aster 6kW unit are disabled on the slave
units for protection. All the queries are still avai lable.
Setup
Current
Sharing
Network
To set up multiple supplies for current share operation, follow these st eps:
1. Power down the units. Connect the CAN ports of all paralleled units a s explained
in “CANbus Setup”.
2. Make load connections. It is recommended to keep l oad cables the same length
if possible. See Figure 3.1.
3. Power up the master.
4. Power up the slaves one at a time.
5. Set the voltage and current on the master, then enable the output.