TM-XDSL-01XN.book Page 26 Tuesday, November 5, 2002 3:22 PM

Specifications and Characteristics

AC Line Input Specifications

AC Line Input Specifications

The input to the power supply requires the following specifications.

AC Line Input

Voltage

Operating

Ranges

Table A.5AC Line Input Specifications

Operating Range

 

nominal 208Vrms (Standard)

190 to 242 Vac 3 φ (3 wire + safety ground)

nominal 400Vrms (with HV-Input option)

342 to 500 Vac 3 φ (3 wire + safety ground)

Frequency Range

47 to 63 Hz

 

 

Maximum Peak In-rush Current at turn on

35 Arms

 

 

Minimum Power Factor1

 

nominal 208Vrms (Standard)

0.95

nominal 400Vrms (with HV-Input option)

0.9

Operating Current

 

nominal 208Vrms (Standard)

 

Maximum2

24 A

Typical3

20 A

Operating Current

 

nominal 400Vrms (with HV-Input option)

 

Maximum4

13 A

Typical5

11 A

1.At nominal input voltage and maximum power

2.At 190Vac input voltage, 55°C ambient temperature and maximum power

3.At 208Vac input voltage, 25°C ambient temperature and maximum power

4.At 342Vac input voltage, 50°C ambient temperature and maximum power

5.At 400Vac input voltage, 25°C ambient temperature and maximum power

26

Operating Manual for XDC Series Slave Power Supply

Page 28
Image 28
Xantrex Technology XDC 40-150SL, XDC 6000, XDC 80-75SL AC Line Input Specifications, AC Line Input Voltage Operating Ranges