TM-XDSL-01XN.book Page 29 Tuesday, November 5, 2002 3:22 PM

Specifications and Characteristics

Output Performance Specifications

8 Hour Drift Temperature Stability1

Voltage

0.02% of Vmax

 

 

Current

0.04% of Imax

 

 

Power

0.1% of Pmax

 

 

Temperature Coefficients

Remote Digital Interface

Voltage Programming

0.04% of Vmax/°C

Current Programming

0.06% of Imax/°C

Power Programming

0.1% of Pmax/°C

Voltage Readback

0.04% of Vmax/°C

Current Readback

0.06% of Imax/°C

Power Readback

0.1% of Pmax/°C

 

 

Switching Frequency

Typical 31 kHz; 62 kHz output ripple

Rise Time

5 to 95% step in output voltage.

Load Condition

Time (Max)

 

 

No Load

100 ms

 

 

Full Load

100 ms

 

 

Fall Time

For a programmed 95% to 5% step in output voltage.

Load Condition

Time (Max)

 

 

No Load 1

3 s

Full Load

50 ms

 

 

1. Fall time is 4s for 300 V and 600 V units.

Time Delay From Power On Until Output Stable

5 s maximum

(Within regulation envelope)

1. At 25°C ±5°C after 30 minutes full load operation

Release 1.0

29

Page 31
Image 31
Xantrex Technology XDC 300-20SL, XDC 6000, XDC 80-75SL, XDC 600-10SL, XDC 60-100SL manual Typical 31 kHz 62 kHz output ripple