Xantrex Technology XPD 120-4.5 Additional Characteristics, Remote Programming and Monitoring

Models: XPD 18-30 XPD 33-16 XPD 120-4.5 XPD 7.5-67 XPD 60-9

1 56
Download 56 pages 43.26 Kb
Page 22
Image 22
Additional Characteristics

Section 1. Features and Specifications

Additional Characteristics

Additional Characteristics

Over Temperature Protection (OTP)

Unit latches off when T > rated maximum.

 

Auto restart when cool

 

 

OVP Control

Adjustable on front panel single turn control.

 

110% setting 5% of rated output

 

 

Switching Frequency

125 kHz (250 kHz output ripple)

 

 

Output Hold-up Time

10 ms @120 Vac input

 

 

Insulation Resistance

Input to chassis: >30 M ohm, with 500 Vdc

 

Output to chassis: >20 M ohm, with

 

1000 Vdc

 

 

Isolation Voltage

Input to output: 1350 Vac

 

 

Remote Programming and Monitoring

Remote S/D and Interlock1

5–15 V signal or TTL-compatible output,

 

selectable logic. TTL input impedance: 2 k

 

(in series with one diode drop)

 

 

Remote Analog Programming (Full

Voltage and current programming inputs

Scale Input)

(source must be floating): 0-10 V voltage

 

sources.

 

Input impedance (V and I): 20 k

 

 

Remote Monitoring

Output voltage and current: 0-10 V

 

Output impedance (V and I): approximately

 

221 ohm; output short circuit current:

 

approximately 20 mA (load must be floating)

 

 

Remote Programming and Monitoring

1% of full scale output for the default range

Accuracy

 

 

 

Maximum Remote Sense Line Drop

7.5 V model: 3 V/line;2

Compensation

18-120 V models: 5 V/line2

Optional Digital Control

RS-232, GPIB interfaces

1.Isolated from power supply output and chassis to 500 V.

2.Line drop must be deduced from supply maximum output.

20

Operating Manual for XPD Series Power Supply

Page 22
Image 22
Xantrex Technology XPD 120-4.5 Additional Characteristics, Remote Programming and Monitoring, Features and Specifications