Remote Sensing

Section 2. Installation

Remote Sensing

Remote Sensing

Remote sensing permits you to shift the regulation point of the power supply from the output terminals to the load or other distribution terminals. It compensates for voltage losses of up to a total of 5 V in the power leads supplying the load (3 V on 7.5 V unit).

For best noise performance, use shielded pair wiring of 16 to 24 AWG for remote sense lines.

Manual background Remove default jumpers (Pins 1-2 and 4-5)

Manual background Connect sense lines as close to load as possible or at point to be regulated

In order to connect the sense wires, follow this procedure:

1.Using a small flat blade screwdriver, remove the two sense jumpers on the J207 connector.

2.Using the appropriate gauge shielded wire (see “Sense Wiring”), connect one end to the load or point at which load is to be regulated.

3.Connect the positive sense line from the load to J207-4 (+SNS) and the return or (-SNS).

Release A