Positive-negative supply To obtain a positive-negative supply, connect the negative output terminal of one supply to the positive terminal of the second supply. The positive output terminal of the first supply now provides a positive voltage relative to the common connection. The negative output terminal of the second supply provides the negative voltage. The current limits can be set independently of each other. The maximum current available in split operation is equal to the rated output of the supplies.

Section 3. Local Operation

Using Multiple Supplies

Positive-negative supply To obtain a positive-negative supply, connect the negative output terminal of one supply to the positive terminal of the second supply. The positive output terminal of the first supply now provides a positive voltage relative to the common connection. The negative output terminal of the second supply provides the negative voltage. The current limits can be set independently of each other. The maximum current available in split operation is equal to the rated output of the supplies.

 

Postive Sense

Load Lines

 

Positive Output

Use the largest gauge and

 

shortest length possible

 

Terminal

 

Negative Output

 

 

Terminal

 

 

Return Sense

Positive Load

 

 

 

Power Supply 1

Terminal

 

Common Load

 

 

 

 

Terminal

 

Postive Sense

Negative Load

 

Terminal

 

Positive Output

 

 

 

Terminal

Load

 

Negative Output

 

Terminal

 

 

Return Sense

 

 

Power Supply 2

 

Figure 3.5

Split Supply Operation of Multiple Supplies (Positive-negative Supply)

Note Split supply operation requires the use of an isolated analog interface card on the slave unit. In this arrangement, one-knob control of both supplies is possible