Installation
2–22 975-0054-01-01
Step 10: Performing Checks Prior to Initial Start-upBefore starting up your inverter, ensure these conditions are met:
❐Chassis ground is properly installed
❐On/Standby switch is in the Standby ( ) position on both the XS400
and S400 Remote Switch
❐Positive (+) battery cable is connected to the positive (+) battery
terminal through the DC fuse and Disconnect or DC circuit breaker
❐Negative (–) battery cable is connected to the negative (–) battery
terminal
❐Battery voltage is within the proper range for this unit
(10.3–15.3 volts DC)
❐DC Fuse is intact (not blown)
Step 11: Connecting the AC Inp ut CordTo connect the AC input cord:
◆Plug the AC input cord into a properly grounded 120 volts AC, 15 or
20 amp receptacle, connected to an external shore power source such
as a utility grid or a generator.
WARNING: Shock hazard
Connect the AC input cord only to a properly grounded
standard 120 volts AC, 15 or 20 amp receptacle. If the correct
type of receptacle is not available, have an electrician install
one.
WARNING: Shock hazard
When the On/Standby switch is in the Standby ( ) position and
the XS400 is connected to shore power, AC voltage will be
present at the output of the inverter.