036-21564-003-A-1005
STATIC RESISTANCES
EXTERNAL STATIC PRESSURE DROP
|
|
|
|
|
| RESISTANCE, IWG |
|
|
| ||
DESCRIPTION |
|
|
|
| CFM |
|
|
|
| ||
|
|
| 1000 | 1200 | 1400 | 1600 | 1800 | 2000 | 2200 | 2400 | 2600 |
Economizer1, 2 |
| 0.07 | 0.08 | 0.09 | 0.11 | 0.13 | 0.15 | 0.17 | 0.20 | 0.23 | |
Electric Heaters1 |
| 5 - 15 KW | 0.04 | 0.05 | 0.06 | 0.07 | 0.08 | 0.10 | 0.12 | 0.14 | 0.16 |
| 20 - 30 KW | 0.06 | 0.07 | 0.08 | 0.09 | 0.11 | 0.13 | 0.15 | 0.17 | 0.20 | |
|
| ||||||||||
Bottom Duct Connections1 |
| 0.06 | 0.07 | 0.08 | 0.09 | 0.10 | 0.11 | 0.12 | 0.14 | 0.16 |
1Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
2The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
HEATER / CFM LIMITATIONS
HEATER |
| UNIT MODEL SIZE, NOMINAL TONS | ||
SIZE | VOLTAGE1 | 3 | 4 | 5 |
NOM. KW |
| MINIMUM SUPPLY AIR CFM | ||
5 |
| 1,100 | 1,300 | 1,600 |
7 |
| 1,100 | 1,300 | 1,600 |
10 | 208 / | 1,200 | 1,300 | 1,600 |
15 | 1,200 | 1,300 | 1,600 | |
20 |
| 1,3002 | 1,3002 | 1,600 |
30 |
| - | - | 1,600 |
5 |
| 1,100 | 1,300 | 1,600 |
7 |
| 1,100 | 1,300 | 1,600 |
10 | 208 / | 1,200 | 1,300 | 1,600 |
15 | 1,200 | 1,300 | 1,600 | |
20 |
| 1,3002 | 1,3002 | 1,600 |
30 |
| - | - | 1,600 |
HEATER |
| UNIT MODEL SIZE, NOMINAL TONS | |||
SIZE | VOLTAGE1 | 3 | 4 | 5 | |
NOM. KW |
| MINIMUM SUPPLY AIR CFM | |||
7 |
| 1,100 | 1,300 | 1,600 | |
10 |
| 1,200 | 1,300 | 1,600 | |
15 | 1,200 | 1,300 | 1,600 | ||
20 |
| 1,300 | 1,300 | 1,600 | |
30 |
| - | - | 1,600 | |
10 |
| 1,200 | 1,300 | 1,600 | |
15 | 1,200 | 1,300 | 1,600 | ||
20 | 1,300 | 1.400 | 1,600 | ||
| |||||
30 |
| - | - | 1,800 |
1208/230 and 460 volt heaters are UL approved. 208/230 and 575 volt heaters are CGA approved.
2CGA minimum is 1,400 CFM.
FIELD WIRING | CONTROL WIRING |
2
1
2Only required on units with supplemental electric heat.
2
3
4
TO REMOTE SENSOR 2TH04702224 IF USED
REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, THE WIRING AND OVERCURRENT PROTECTION
POWER WIRING
REFER TO ELECTRICAL DATA
TABLES TO SIZE THE
DISCONNECT SWITCH, THE
WIRING AND OVERCURRENT
PROTECTION
10 | Unitary Products Group |