036-21564-003-A-1005

UNIT DIMENSIONS (BCH - 3, 4 & 5 TON)

OUTDOOR COIL

(Direct-Drive Units)

RETURN AIR

SUPPLY AIR

OUTDOOR

OUTDOOR AIR (Economizer)

All dimensions are in inches. They are sub- ject to change without notice. Certified di- mensions will be provided upon request.

UTILITIES ENTRY DATA

 

KNOCKOUT

 

HOLE

SIZE

USED FOR

 

(DIA.)

 

A

7/8" *

Control Wiring

(Side or Bottom)**

 

 

B

2" *

Power Wiring

(Side or Bottom)

 

 

*Knockouts in the bottom of the unit can be located by the slice in the insulation.

**Do not remove the 2" knockout ring.

CLEARANCES

Front

24"

 

12" (Less Economizer)

Back

36" (With Economizer or Fixed

 

Air/Motorized Air Damper)

Left Side (Filter Access)

24" (Less Economizer)

36" (With Economizer)

 

Right Side (OD Coil)

24"

Below Unit1

0"

Above Unit2

72" (For Outdoor Air Discharge)

NOTE:

Units and ductwork are approved for zero clearance to combustible materials when

equipped with electric heaters.

1Units may be installed on combustible floors made from wood or class A, B or C roof covering material.

2Units must be installed oudoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.

Unitary Products Group

15

Page 15
Image 15
York 2000 warranty Direct-Drive Units, Knockout Hole Size Used for, DIA Control Wiring Side or Bottom Power Wiring