UNIT DIMENSIONS (BCH - 3, 4 & 5 TON)

036-21564-003-A-1005

UNIT DIMENSIONS (BCH - 3, 4 & 5 TON)

OUTDOOR COIL

(Direct-Drive Units)

RETURN AIR

SUPPLY AIR

OUTDOOR

OUTDOOR AIR (Economizer)

All dimensions are in inches. They are sub- ject to change without notice. Certified di- mensions will be provided upon request.

UTILITIES ENTRY DATA

 

KNOCKOUT

 

HOLE

SIZE

USED FOR

 

(DIA.)

 

A

7/8" *

Control Wiring

(Side or Bottom)**

 

 

B

2" *

Power Wiring

(Side or Bottom)

 

 

*Knockouts in the bottom of the unit can be located by the slice in the insulation.

**Do not remove the 2" knockout ring.

CLEARANCES

Front

24"

 

12" (Less Economizer)

Back

36" (With Economizer or Fixed

 

Air/Motorized Air Damper)

Left Side (Filter Access)

24" (Less Economizer)

36" (With Economizer)

 

Right Side (OD Coil)

24"

Below Unit1

0"

Above Unit2

72" (For Outdoor Air Discharge)

NOTE:

Units and ductwork are approved for zero clearance to combustible materials when

equipped with electric heaters.

1Units may be installed on combustible floors made from wood or class A, B or C roof covering material.

2Units must be installed oudoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.