York 2000 warranty COOLING CAPACITIES - 4 TON BCH048

Models: 2000

1 24
Download 24 pages 58.42 Kb
Page 5
Image 5
COOLING CAPACITIES - 4 TON (BCH048)

036-21564-003-A-1005

COOLING CAPACITIES - 4 TON (BCH048)

Air On

 

 

 

 

 

 

Temperature of Air on Outdoor Coil

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

85 °F

 

 

 

 

 

 

 

 

 

 

95 °F

 

 

 

 

 

 

Coil

 

 

 

 

 

 

 

1

, MBH

 

 

 

 

 

Sensible Capacity

1

, MBH

 

 

 

 

Total

Power

 

Sensible Capacity

 

Total

Power

 

 

 

 

CFM

 

WB

Cap.1

Input2

 

Entering Dry Bulb, °F

 

Cap.1

Input2

 

 

Entering Dry Bulb, °F

 

 

°F

MBH

KW

86

83

80

77

 

74

71

68

MBH

KW

 

86

83

80

77

74

71

68

 

 

 

 

 

 

72

56

4.1

42

36

31

26

 

-

 

-

-

53

4.5

 

40

35

29

24

-

 

-

-

2000

 

67

53

4.0

48

47

41

36

 

30

25

-

51

4.4

 

46

45

41

35

30

24

-

 

62

49

4.0

49

49

48

44

 

38

33

28

46

4.3

 

46

46

45

41

35

30

24

 

 

 

 

 

 

57

49

3.9

49

49

49

44

 

38

33

28

46

4.3

 

46

46

46

41

35

30

24

 

 

72

55

4.0

40

35

30

25

 

-

 

-

-

53

4.4

 

38

33

28

23

-

 

-

-

1800

 

67

52

4.0

47

44

39

34

 

29

24

-

51

4.4

 

44

44

39

34

29

24

-

 

62

48

3.9

48

48

47

43

 

38

33

28

47

4.3

 

47

47

45

40

36

31

26

 

 

 

 

 

 

57

48

3.9

48

48

48

43

 

38

33

28

45

4.2

 

45

45

45

40

35

30

25

 

 

72

53

4.0

37

33

28

24

 

-

 

-

-

52

4.4

 

36

32

27

23

-

 

-

-

1600

 

67

51

4.0

46

42

37

33

 

28

24

-

50

4.3

 

44

43

38

34

29

25

-

 

62

47

3.9

47

47

46

41

 

37

32

28

45

4.2

 

45

45

44

40

36

31

27

 

 

 

 

 

 

57

47

3.9

47

47

47

42

 

38

33

29

44

4.1

 

44

44

44

40

36

31

27

 

 

72

52

4.0

34

30

26

22

 

-

 

-

-

49

4.3

 

33

29

25

21

-

 

-

-

1400

 

67

49

3.9

42

38

34

30

 

26

22

-

47

4.2

 

42

38

34

30

26

22

-

 

62

46

3.8

46

45

42

38

 

34

30

26

43

4.1

 

43

42

40

36

32

28

24

 

 

 

 

 

 

57

45

3.8

45

45

43

39

 

35

31

27

42

4.1

 

42

42

40

36

32

28

24

 

 

72

50

3.9

31

27

24

20

 

-

 

-

-

47

4.2

 

29

25

22

18

-

 

-

-

1200

 

67

47

3.9

38

35

31

28

 

24

21

-

45

4.2

 

37

34

30

27

23

20

-

 

62

44

3.8

44

42

39

35

 

32

28

25

40

4.1

 

40

39

36

32

29

25

22

 

 

 

 

 

 

57

44

3.7

44

43

39

36

 

32

29

25

40

4.0

 

40

39

36

32

29

25

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air On

 

 

 

 

 

 

Temperature of Air on Outdoor Coil

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

105 °F

 

 

 

 

 

 

 

 

 

 

115 °F

 

 

 

 

 

 

Coil

 

 

 

 

 

 

 

1

, MBH

 

 

 

 

 

Sensible Capacity

1

, MBH

 

 

 

 

Total

Power

 

Sensible Capacity

 

Total

Power

 

 

 

 

CFM

 

WB

Cap.1

Input2

 

Entering Dry Bulb, °F

 

Cap.1

Input2

 

 

Entering Dry Bulb, °F

 

 

°F

MBH

KW

86

83

80

77

 

74

71

68

MBH

KW

 

86

83

80

77

74

71

68

 

 

 

 

 

 

72

51

4.9

40

35

29

24

 

-

 

-

-

49

5.2

 

39

34

29

23

-

 

-

-

2000

 

67

46

4.7

42

42

39

34

 

28

23

-

41

5.0

 

40

40

37

32

26

21

-

 

62

43

4.6

43

43

42

37

 

32

27

21

40

4.9

 

40

40

39

34

29

23

18

 

 

 

 

 

 

57

43

4.6

43

43

43

38

 

32

28

22

40

4.8

 

40

40

40

34

30

24

19

 

 

72

50

4.8

38

33

28

23

 

-

 

-

-

47

5.1

 

37

32

27

22

-

 

-

-

1800

 

67

45

4.7

41

41

37

32

 

27

22

-

40

4.9

 

37

36

35

30

25

20

-

 

62

42

4.6

42

42

41

37

 

32

27

22

39

4.8

 

39

39

37

34

29

24

19

 

 

 

 

 

 

57

42

4.5

42

42

42

37

 

33

27

23

38

4.7

 

38

38

38

33

30

25

20

 

 

72

49

4.8

35

31

26

22

 

-

 

-

-

46

5.1

 

34

29

25

20

-

 

-

-

1600

 

67

44

4.6

40

40

35

31

 

26

22

-

39

4.9

 

36

36

32

28

23

19

-

 

62

41

4.5

41

41

40

35

 

32

27

23

37

4.7

 

37

37

36

33

28

24

19

 

 

 

 

 

 

57

41

4.4

41

41

41

36

 

32

28

23

37

4.7

 

37

37

37

34

28

25

20

 

 

72

47

4.7

32

28

24

20

 

-

 

-

-

44

5.0

 

31

27

23

19

-

 

-

-

1400

 

67

42

4.5

38

36

32

28

 

24

20

-

37

4.8

 

36

34

30

26

21

17

-

 

62

39

4.4

39

38

37

33

 

28

25

20

36

4.7

 

36

35

34

30

26

22

18

 

 

 

 

 

 

57

39

4.4

39

39

37

33

 

29

25

21

36

4.6

 

36

36

34

31

26

23

19

 

 

72

44

4.6

28

25

21

18

 

-

 

-

-

42

4.9

 

28

24

21

17

-

 

-

-

1200

 

67

40

4.5

36

32

29

25

 

22

18

-

36

4.7

 

34

31

27

24

20

17

-

 

62

38

4.4

38

36

34

29

 

27

22

20

35

4.6

 

35

34

30

28

24

20

17

 

 

 

 

 

 

57

37

4.3

37

37

34

30

 

27

23

20

35

4.6

 

35

35

31

29

24

21

18

1These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

2These ratings include the compressor and the outdoor fan motors but not the supply air blower motor. The total outdoor fan motor power input is 0.35 KW. Refer to the Blower Performance Table for the KW of the supply air blower motor.

NOMINAL RATING

ALL SENSIBLE CAPACITY

Unitary Products Group

5

Page 5
Image 5
York 2000 warranty COOLING CAPACITIES - 4 TON BCH048