York 2000 warranty Physical Data Basic Units, Capacity Ratings, Sound Power Ratings

Models: 2000

1 24
Download 24 pages 58.42 Kb
Page 3
Image 3
RATINGS

036-21564-003-A-1005

RATINGS

CAPACITY RATINGS

 

 

 

 

 

 

ARI RATINGS (SEE NOTE 1)

 

 

 

 

 

 

NOMINAL

 

MODEL

 

COOLING

 

 

SOUND

 

HEATING CAPACITY

ELECTRIC HEAT CAPACITY

BCH

PERFORMANCE

 

RATING

HSPF

47

°

F

17

°

F

(SEE NOTE 3)

 

 

(SEE NOTE 2)

 

KW

 

 

 

 

 

 

 

 

 

 

 

 

 

MBH

 

SEER

 

EER

 

bels

 

MBH

 

COP

MBH

 

COP

240V

480V

600V

036

39

 

10.00

 

9.20

 

8.6

7.3

39.0

 

3.0

23.0

 

2.1

5, 7, 10, 15 & 20

7,10,15 & 20

10, 15 & 20

048

48

 

10.20

 

9.25

 

8.6

6.7

48.0

 

3.0

26.4

 

2.0

5, 7, 10, 15 & 20

7,10,15 & 20

10, 15 & 20

060

59

 

10.00

 

9.20

 

8.4

7.0

59.0

 

3.0

36.0

 

2.1

5,7,10,15,20 & 30

7,10,15,20 & 30

10,15,20 & 30

NOTE: 1. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.

2.Rated in accordance with ARI Standard 270.

3.Heaters available as accessories - all with single point power supply.

SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.

EER = Energy Efficiency Ratio-the cooling capacity in BTU's per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).

COP = Coefficient of Performance - the total heating capacity provided by the refrigeration system, including circulating fan heat but excluding supplementary resistance (BTU's per hour) divided by the total electric input (watts) x 3.412.

SOUND POWER RATINGS

 

 

ESP

Blower

 

 

 

 

Sound Power (dB 10-12Watts)

 

 

 

Unit

CFM

 

 

Octave Band Centerline Frequency (Hz)

 

 

SWL

dB(A)

 

 

 

 

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IWG

Speed

KW

63

125

 

250

500

1000

2000

 

4000

8000

dB(A)

@ 10 ft*

 

 

 

 

 

 

038

1200

0.60

LOW

0.60

84

84

 

74

67

69

62

 

57

52

74

41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

1600

0.55

HIGH

0.80

85

85

 

75

68

70

63

 

58

53

75

42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

2000

0.45

HIGH

1.00

86

86

 

76

69

71

64

 

59

54

76

43

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*At a distance of 10 ft from the blower

NOTE: These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacturer has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.

PHYSICAL DATA

BASIC UNITS

 

MODELS

 

BCH

 

 

036

048

060

 

 

SUPPLY AIR

CENTRIFUGAL BLOWER (Dia. x Wd. in.)

12 x 10

12 x 10

12 x 10

FAN MOTOR HP (DIRECT-DRIVE)

1

3

1

BLOWER

2

4

FAN MOTOR HP (BELT-DRIVE)

1.5

1.5

1.5

 

INDOOR

ROWS DEEP

4

3

3

FINS PER INCH

16

15

15

COIL

FACE AREA (Sq. Ft.)

4.3

5.1

5.1

 

OUTDOOR

PROPELLER DIA. (in.)

22

22

24

FAN MOTOR HP

1

1

1

FAN

3

2

2

NOM. CFM TOTAL

4300

4200

4500

 

OUTDOOR

ROWS DEEP

1

1

1

FINS PER INCH

20

20

20

COIL

FACE AREA (Sq. Ft.)

17.1

17.1

17.1

 

AIR

QUANTITY PER UNIT (15" x 20" x 1")

2

2

2

FILTERS

QUANTITY PER UNIT (14" X 25" X 1")

1

1

1

(SEE NOTE)

TOTAL FACE AREA (sq. ft.)

6.6

6.6

6.6

CHARGE

REFRIGERANT 22 (lbs./oz.)

7/12

9/2

8/4

COMPRESSOR

HERMETIC, RECIPROCATING (Qty)

1

1

1

NOTE: Filter racks can accommodate 1" or 2" thick filters.

Unitary Products Group

3

Page 3
Image 3
York 2000 warranty Physical Data Basic Units, Capacity Ratings, Sound Power Ratings