York DM090 Phasing, Blower Rotation, Supply Air Limitations, Belt Tension, Belt Adjustment

Models: DM090

1 44
Download 44 pages 9.47 Kb
Page 24
Image 24
PHASING

035-17311-003-A-0704

PHASING

Predator® units are properly phased at the factory. Check for proper compressor rotation. If the blower or compressors rotate in the wrong direction at start-up, the electrical connec- tion to the unit is misphased. Change the phasing of the Field

Line Connection at the factory or field supplied discon- nect to obtain proper rotation. (Scroll compressors operate in only one direction. If the scroll is drawing low amperage, has similar suction and discharge pressures, or producing a high noise level, the scroll is misphased.)

Scroll compressors require proper rotation to oper- ate correctly. Units are properly phased at the fac- tory. Do not change the internal wiring to make the blower condenser fans, or compressor rotate cor- rectly.

BLOWER ROTATION

Check for proper supply air blower rotation. If the blower is rotating backwards, the line voltage at the unit point of power connection is misphased (See ‘PHASING’).

TABLE 16: SUPPLY AIR LIMITATIONS

Unit Size

Minimum

Maximum

 

 

 

090

2250

3750

 

 

 

120

3000

5000

 

 

 

150

3750

6250

 

 

 

BELT TENSION

The tension on the belt should be adjusted as shown in Figure 22.

ABLOWER ROTATION

A

C*

* NEVER LOOSEN

A TABLE 16: SUPPLY AIR LIMITATIONS

B

SPAN LENGTH

DEFL. FORCE

FIGURE 22 - BELT ADJUSTMENT

Procedure for adjusting belt tension:

1.Loosen six nuts (top and bottom) A.

2.Adjust by turning (B).

3.Never loosen nuts (C).

4.Use belt tension checker to apply a perpendicular force to one belt at the midpoint of the span as shown. Deflection distance of 4mm (5/32”) is obtained.

To determine the deflection distance from normal position, use a straight edge from sheave to sheave as reference line. The recommended deflection force is as follows:

Tension new belts at the max. deflection force rec- ommended for the belt section. Check the belt ten- sion at least two times during the first 24 hours of operation. Any retensioning should fall between the min. and max. deflection force values.

5. After adjusting retighten nuts (A).

24

Unitary Products Group

Page 24
Image 24
York DM090 installation manual Phasing, Blower Rotation, Supply Air Limitations, Belt Tension, Belt Adjustment