York DM090 Unit Control Board Flash Codes, Basic Troubleshooting Flowchart, 035-17311-003-A-0704

Models: DM090

1 44
Download 44 pages 9.47 Kb
Page 40
Image 40
TABLE 37: UNIT CONTROL BOARD FLASH CODES

035-17311-003-A-0704

TABLE 37: UNIT CONTROL BOARD FLASH CODES

Flash Code

Description

On Steady

Control Failure - Replace Control

Heart Beat

Normal Operation

 

 

1 Flash

Not Applicable

 

 

2 Flashes

Control waiting ASCD*

3 Flashes

HPS1 - Compressor Lock out

 

 

4 Flashes

HPS2 - Compressor Lock out

 

 

5 Flashes

LPS1 - Compressor Lock out

 

 

6 Flashes

LPS2 - Compressor Lock out

 

 

7 Flashes

FS1 - Compressor Lock out

 

 

8 Flashes

FS2 - Compressor Lock out

 

 

9 Flashes

Ignition Control Locked Out/

Ignition Control Failure / Limit Switch Trip / No Jumper Plug in Heat Section

 

 

 

10 Flashes

Compressors Locked Out On Low

Outdoor Air Temperature*

 

11 Flashes

Compressors Locked Out Because The

Economizer Is Using Free Cooling*

 

12 Flashes

Fan Overload Switch Trip - Not Applicable On This Unit *

 

 

13 Flashes

Compressor Held Off Due To Low Voltage*

 

 

14 Flashes

EEPROM Storage Failure (Control Failure)

 

 

OFF

No Power or Control Failure

*. These flash codes do not represent alarms.

 

Monitored

No

 

 

Programming?

No

 

Call for

No

Loss of

Yes

 

Systems

 

 

 

 

 

 

 

Call for

 

 

 

 

 

 

 

 

Heating?

 

 

 

Problem?

 

 

 

 

 

 

 

 

 

 

 

Heating?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

Yes

 

 

Yes

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Program

 

 

 

 

 

 

 

 

 

 

 

Trip/Failure

 

 

 

 

 

Unit

 

 

 

Call for

 

 

 

 

 

 

 

 

 

 

 

Control

 

 

 

 

 

Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat Off

Call for 2nd

Stage

Cooling

No

Monitor

 

 

 

 

No

Turn off ID

Yes

Fan on

 

Blower Motor

 

>30 secs?

 

 

Yes

 

No

Lossof Call

 

 

 

 

for ID Blower?

 

 

 

 

 

Energize ID

 

 

 

 

 

Blower Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

Fan off

 

 

 

 

 

 

 

 

 

 

>10 secs?

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

No

Call for

 

 

 

 

 

 

 

 

ID Blower?

Call for

Yes

Cooling?

 

 

No

 

 

 

 

 

 

No

Loss of Call

Yes

 

for Cooling?

 

First

Stage?

Yes

Call for 1st

Stage

Cooling

Cool Off

FIGURE 24 - BASIC TROUBLESHOOTING FLOWCHART

40

Unitary Products Group

Page 40
Image 40
York DM090 installation manual Unit Control Board Flash Codes, Basic Troubleshooting Flowchart, 035-17311-003-A-0704