York R-407C manual Cooling Performance Data - 60 Ton Model, Air On Condenser Coil

Models: R-407C

1 44
Download 44 pages 60.24 Kb
Page 16
Image 16
Cooling Performance Data – 60 Ton Model

Cooling Performance Data – 60 Ton Model

TABLE 4 – COOLING PERFORMANCE DATA – 60 TON MODEL

85° AIR ON CONDENSER COIL

 

 

 

 

 

 

 

CAPACITY (MBH) AT ENTERING DRY BULB (°F)

 

 

 

 

 

CFM

ENTERING

 

90

86

 

83

 

 

80

 

77

 

74

WB (°F)

CAP

 

SHC

CAP

 

SHC

CAP

 

SHC

CAP

 

SHC

CAP

 

SHC

CAP

 

SHC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

804

 

495

804

 

461

801

 

277

798

 

383

792

 

344

 

14000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

736

 

586

728

 

522

729

 

339

727

 

440

725

 

408

723

 

377

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

689

 

689

663

 

663

658

 

442

656

 

543

647

 

493

654

 

424

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

846

 

609

840

 

538

837

 

410

833

 

426

827

 

372

 

18000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

795

 

720

773

 

632

771

 

504

769

 

519

767

 

468

761

 

415

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

771

 

771

740

 

740

725

 

617

704

 

630

700

 

572

699

 

502

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

867

 

666

858

 

576

855

 

477

851

 

448

845

 

386

 

21000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

824

 

787

795

 

687

792

 

587

790

 

558

787

 

498

780

 

434

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

813

 

813

779

 

779

759

 

705

728

 

673

726

 

611

722

 

541

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

888

 

722

876

 

614

872

 

544

868

 

470

862

 

401

 

24000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

854

 

854

818

 

742

814

 

670

810

 

598

808

 

528

799

 

453

 

62

854

 

854

817

 

817

792

 

792

752

 

716

752

 

651

744

 

580

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

897

 

748

884

 

632

880

 

574

876

 

480

870

 

407

 

27000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

867

 

867

828

 

767

823

 

708

820

 

616

818

 

541

808

 

461

 

62

873

 

873

835

 

835

808

 

817

763

 

736

764

 

669

755

 

598

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Rated performance is at sea level. Cooling capacities are gross cooling capacity.

95° AIR ON CONDENSER COIL

 

 

 

 

 

 

 

CAPACITY (MBH) AT ENTERING DRY BULB (°F)

 

 

 

 

 

CFM

ENTERING

 

90

86

 

83

 

 

80

 

77

 

74

WB (°F)

CAP

 

SHC

CAP

 

SHC

CAP

 

SHC

CAP

 

SHC

CAP

 

SHC

CAP

 

SHC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

773

 

491

771

 

442

769

 

336

769

 

368

763

 

331

 

14000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

723

 

527

692

 

464

703

 

397

703

 

432

699

 

437

696

 

363

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

671

 

671

645

 

645

631

 

474

642

 

505

655

 

416

673

 

318

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

814

 

599

808

 

524

804

 

434

802

 

414

797

 

361

 

18000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

775

 

678

752

 

570

745

 

529

742

 

508

736

 

455

732

 

402

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

750

 

750

719

 

719

699

 

620

684

 

604

682

 

550

681

 

494

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

834

 

652

827

 

565

822

 

482

819

 

438

814

 

376

 

21000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

802

 

753

783

 

623

766

 

594

761

 

546

755

 

463

751

 

421

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

789

 

789

756

 

756

732

 

693

706

 

653

696

 

616

685

 

582

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

854

 

706

846

 

607

840

 

531

835

 

461

831

 

391

 

24000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

828

 

828

813

 

675

788

 

660

780

 

584

774

 

472

769

 

441

 

62

828

 

828

793

 

793

766

 

766

727

 

703

709

 

683

689

 

670

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

864

 

730

854

 

626

848

 

553

843

 

471

838

 

397

 

27000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

840

 

863

827

 

699

797

 

691

789

 

601

782

 

476

778

 

450

 

62

846

 

846

810

 

810

782

 

788

737

 

726

716

 

714

690

 

710

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Rated performance is at sea level. Cooling capacities are gross cooling capacity.