FORM 100.50-EG1

TABLE 10 – SUPPLY AND EXHAUST FAN MOTOR (ODP OR TEFC)

High Efficiency

 

 

NOMINAL VOLTAGE

 

MOTOR

208V

230V

460V

575V

HP

FLA

FLA

FLA

FLA

5.0

14.0

13.4

6.7

5.3

7.5

22.2

21.6

10.8

8.2

10.0

28.5

28.4

14.2

11.4

15.0

44.8

39.0

19.5

16.0

20.0

61.0

50.0

25.0

20.0

25.0

74.0

60.0

30.0

24.2

30.0

87.0

76.0

38.0

30.3

40.0

113.0

95.6

47.8

38.0

 

 

 

 

 

Premium Efficiency

 

 

NOMINAL VOLTAGE

 

MOTOR

208V

230V

460V

575V

HP

FLA

FLA

FLA

FLA

5.0

14.9

13.6

6.8

5.5

7.5

22.5

20.0

10.0

7.9

10.0

29.2

25.8

12.9

10.3

15.0

41.5

36.0

18.0

14.5

20.0

55.0

48.0

24.0

19.3

25.0

71.0

61.0

30.5

24.5

30.0

85.5

74.0

37.0

30.0

40.0

109.0

96.0

48.0

38.0

TABLE 11 – CONDENSER FAN MOTORS / EACH

 

 

NOMINAL VOLTAGE

 

NOMINAL

208V

230V

460V

575V

 

 

 

 

 

TONS

FLA

FLA

FLA

FLA

50

7.5

6.8

3.4

2.7

55

7.5

6.8

3.4

2.7

60

7.5

6.8

3.4

2.7

65

7.5

6.8

3.4

2.7

 

 

 

 

 

TABLE 12 – CONTROLS AND CONVENIENCE OUTLET

 

NOMINAL VOLTAGE

DESCRIPTION

208V

230V

460V

575V

AMPS

AMPS

AMPS

AMPS

 

Control Transformer

3.6

3.3

1.6

3.3

Convenience Outlet

9.6

8.7

4.3

3.5

 

 

 

 

 

YORK INTERNATIONAL

25

Page 25
Image 25
York R-407C Supply and Exhaust FAN Motor ODP or Tefc, High Efficiency, Premium Efficiency, Condenser FAN Motors / Each