York R-407C Power Wiring continued, Single-Point Power Supply Wiring With Non-Fused Disconnect

Models: R-407C

1 44
Download 44 pages 60.24 Kb
Page 32
Image 32
Power Wiring (continued)

Power Wiring (continued)

SINGLE-POINT POWER SUPPLY WIRING

WITH NON-FUSED DISCONNECT

Field Power Supply

NOTES:

Electrical / Controls Box

Power Side

Molded

1L1 1L2 1L3

 

GND

Case

 

Disconnect

 

 

 

 

 

 

 

 

 

 

Switch

 

 

 

 

 

 

 

 

 

 

Line 1

Line 2

Line 3

Earth

Ground

Control Side

Wiring Terminal

Block

LD06415

1.All field wiring must be provided through a field-supplied fused disconnect switch to the unit terminals (or optional molded disconnect switch).

2.All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.

3.Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).

4.Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)

5.Use copper conductors only.

6.On units with an optional disconnect switch, the supplied disconnect switch is a “Disconnecting Means” as defined in the N.E.C. Section 100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect switch is not intended to be a Load Break Device.

FIG. 3 – SINGLE-POINT POWER SUPPLY WIRING WITH NON-FUSED DISCONNECT

32

YORK INTERNATIONAL

Page 32
Image 32
York R-407C manual Power Wiring continued, Single-Point Power Supply Wiring With Non-Fused Disconnect, Field Power Supply