Electrical Data

Electrical Data

ELECTRICAL SERVICE SIZING

In order to use the electrical service required for the cooling only Eco2 rooftop, use the appropriate calcula- tions listed below from U.L. 1995. Based on the operat- ing mode and configuration of the rooftop, the calcula- tions will yield different MCA (minimum circuit ampac- ity), and MOP (maximum overcurrent protection).

Using the following load definitions and calculations, determine the correct electrical sizing for your unit. All concurrent load conditions must be considered in the calculations, and you must use the highest value for any combination of loads.

Load Definitions:

LOAD1 is the current of the largest motor – com- pressor or fan motor.

LOAD2 is the sum of the remaining motor currents that may run concurrently with LOAD1 (i.e., exhaust fan motor).

TABLE 9 – COMPRESSORS

LOAD3 is the current of the electric heaters – zero for cooling only units.

LOAD4 is the sum of any remaining currents greater than or equal to 1.0 amp

Use the following calculations to determine MCA and MOP for units supplied with a single-point power connection:

MCA = (1.25 x LOAD1) + LOAD2 + LOAD4

MOP = (2.25 x LOAD1) + LOAD2 + LOAD4

If the MOP does not equal a standard current rating of an overcurrent protective device, then the marked maxi- mum rating is to be the next lower standard rating. How- ever, if the device selected for MOP is less than the MCA, then select the lowest standard maximum fuse size greater than or equal to the MCA.

 

COMPRESSOR

 

 

 

 

NOMINAL VOLTAGE

 

 

 

 

 

QUANTITY

 

208V

 

230V

460V

 

 

575V

 

PER

MODEL

 

 

 

MODEL

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

RLA*

 

LRA*

RLA*

 

LRA*

RLA*

 

LRA*

RLA*

 

LRA*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

4

SZ160

54.0

 

265.0

48.8

 

265.0

24.2

 

135.0

19.4

 

120.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

4

SZ160

54.0

 

265.0

48.8

 

265.0

24.2

 

135.0

19.4

 

120.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

4

SZ185

62.3

 

380.0

56.3

 

380.0

27.9

 

175.0

22.3

 

140.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

4

SZ185

62.3

 

380.0

56.3

 

380.0

27.9

 

175.0

22.3

 

140.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Values shown are per compressor