Power Wiring

FORM 100.50-EG1

Power Wiring

SINGLE-POINT POWER SUPPLY WIRING

Field Power Supply

Electrical / Controls Box

Power Side

1L1 1L2 1L3

GND

TB1

Line 1

Line 2

Line 3

Earth

Ground

Control Side

Wiring Terminal

Block

LD06414

NOTES:

1.All field wiring must be provided through a field-supplied fused disconnect switch to the unit terminals (or optional molded disconnect switch).

2.All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.

3.Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).

4.Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)

5.Use copper conductors only.

6.On units with an optional disconnect switch, the supplied disconnect switch is a “Disconnecting Means” as defined in the N.E.C. Section 100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect switch is not intended to be a Load Break Device.

FIG. 2 – SINGLE-POINT POWER SUPPLY WIRING

YORK INTERNATIONAL

31

Page 31
Image 31