HEATING PERFORMANCE - With Air Handler (Continued)
UNIT | AIR | COIL1 |
|
| ARI HEATING2 |
|
| |||
MODEL* | HANDLER | MODEL |
| 47°F |
|
| 17°F |
| HSPF | |
|
|
| MBH | COP | KW | MBH | COP | KW | STD | |
| 13 SEER | HP WITH AV / SV / F*FV - VARIABLE SPEED |
|
|
|
| ||||
THGD18S41S1 | AV24 | – | 16.8 | 3.62 | 1.36 | 11.5 | 3.18 | 1.06 | 8.00 | |
THGD24S41S1 | AV24 | – | 22.4 | 3.72 | 1.76 | 12.4 | 2.50 | 1.45 | 8.00 | |
AV36 | – | 22.8 | 3.72 | 1.80 | 12.4 | 2.50 | 1.45 | 8.00 | ||
| ||||||||||
THGD30S41S1 | AV36 | – | 27.6 | 3.64 | 2.22 | 16.0 | 2.50 | 1.88 | 8.00 | |
THGD36S41S1 | AV36 | – | 35.0 | 3.58 | 2.87 | 20.8 | 2.46 | 2.48 | 8.00 | |
THGD42S41S1 | AV/SV48 | – | 41.0 | 3.84 | 3.13 | 27.2 | 2.66 | 3.00 | 8.00 | |
| AV/SV48 | – | 50.5 | 3.62 | 4.09 | 30.0 | 2.42 | 3.63 | 8.00 | |
THGD48S41S1 | AV/SV60 | – | 50.5 | 3.62 | 4.09 | 30.2 | 2.40 | 3.69 | 8.00 | |
| F4FV060 | – | 50.5 | 3.62 | 4.09 | 30.2 | 2.40 | 3.69 | 8.00 | |
|
| 13 SEER HP WITH AHP | / SHP / | F*FP |
|
|
|
|
| |
THGD18S41S1 | AHP18 | – | 17.0 | 3.38 | 1.47 | 8.2 | 2.16 | 1.11 | 7.70 | |
F4FP24 | – | 17.0 | 3.34 | 1.49 | 12.5 | 3.04 | 1.21 | 7.70 | ||
| ||||||||||
THGD24S41S1 | AHP30 | – | 23.2 | 3.40 | 2.00 | 12.6 | 2.24 | 1.65 | 7.70 | |
F4FP030 | – | 23.2 | 3.40 | 2.00 | 12.6 | 2.24 | 1.65 | 7.70 | ||
| ||||||||||
THGD30S41S1 | AHP36 | – | 28.2 | 3.40 | 2.43 | 16.6 | 2.32 | 2.10 | 7.70 | |
F4FP040 | – | 28.0 | 3.32 | 2.47 | 16.4 | 2.28 | 2.11 | 7.70 | ||
| ||||||||||
THGD36S41S1 | AHP36 | – | 35.0 | 3.40 | 3.02 | 21.0 | 2.40 | 2.56 | 8.00 | |
F4FP045 | – | 35.0 | 3.40 | 3.02 | 21.6 | 2.42 | 2.62 | 8.00 | ||
| ||||||||||
| AHP/SHP48 | – | 41.0 | 3.32 | 3.62 | 28.2 | 2.36 | 3.50 | 8.00 | |
THGD42S41S1 |
|
|
|
|
|
|
|
|
| |
F4FP045 | – | 41.0 | 3.68 | 3.27 | 27.8 | 2.56 | 3.18 | 8.00 | ||
| F5FP048 | – | 41.0 | 3.68 | 3.27 | 27.6 | 2.58 | 3.14 | 8.00 | |
| AHP/SHP60 | – | 50.5 | 3.58 | 4.13 | 30.2 | 2.40 | 3.69 | 8.00 | |
THGD48S41S1 |
|
|
|
|
|
|
|
|
| |
F5FP048 | – | 50.5 | 3.46 | 4.28 | 30.6 | 2.32 | 3.87 | 8.00 | ||
| F5FP060 | – | 50.5 | 3.60 | 4.11 | 30.2 | 2.40 | 3.69 | 8.00 |
1.Rated CFM same as for cooling.
2.Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation.
CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period.
— = Not Applicable.