COOLING CAPACITY - With Air Handler Coils (Continued)
UNIT | AIR HANDLER |
| COIL |
|
|
| COOLING |
|
| ||
|
|
|
| RATED |
| NET MBH |
|
| |||
MODEL | MODEL |
| W |
| MODEL1 |
| SEER | EER | |||
|
| CFM |
| TOTAL | SENS. | ||||||
|
|
|
|
|
|
|
|
| |||
|
| 13 SEER HP WITH AV / SV / F*FV - VARIABLE SPEED |
|
|
| ||||||
THGD18S41S1 | AV24 |
| 17 |
| – | 550 |
| 17.0 | 13.0 | 14.00 | 12.00 |
THGD24S41S1 | AV24 |
| 17 |
| – | 750 |
| 23.0 | 17.2 | 14.00 | 12.00 |
AV36 |
| 21 |
| – | 750 |
| 23.0 | 18.0 | 14.00 | 12.00 | |
|
|
|
| ||||||||
THGD30S41S1 | AV36 |
| 21 |
| – | 1000 |
| 29.0 | 24.4 | 14.00 | 12.00 |
THGD36S41S1 | AV36 |
| 21 |
| – | 1250 |
| 35.0 | 28.0 | 13.50 | 11.50 |
THGD42S41S1 | AV/SV48 |
| 24 |
| – | 1400 |
| 41.5 | 32.0 | 14.00 | 12.00 |
| AV/SV48 |
| 24 |
| – | 1600 |
| 47.5 | 36.2 | 14.00 | 11.80 |
THGD48S41S1 |
|
|
|
|
|
|
|
|
|
|
|
AV/SV60 |
| 24 |
| – | 1650 |
| 47.5 | 36.6 | 14.00 | 11.80 | |
| F4FV060 |
| 24 |
| – | 1600 |
| 47.5 | 36.2 | 14.00 | 11.80 |
|
|
|
| 13 | SEER HP WITH AHP | / SHP / F*FP |
|
|
|
|
|
THGD18S41S1 | AHP18 |
| 17 |
| – | 600 |
| 17.0 | 12.7 | 13.00 | 11.00 |
F4FP024 |
| 17 |
| – | 600 |
| 17.0 | 12.6 | 13.00 | 11.00 | |
|
|
|
| ||||||||
THGD24S41S1 | AHP30 |
| 17 |
| – | 800 |
| 23.0 | 17.2 | 13.00 | 11.00 |
F4FP030 |
| 17 |
| – | 800 |
| 23.0 | 16.9 | 13.00 | 11.00 | |
|
|
|
| ||||||||
THGD30S41S1 | AHP36 |
| 21 |
| – | 1000 |
| 29.0 | 23.2 | 13.00 | 11.00 |
F4FP040 |
| 21 |
| – | 1000 |
| 29.0 | 22.6 | 13.00 | 11.00 | |
|
|
|
| ||||||||
THGD36S41S1 | AHP36 |
| 21 |
| – | 1200 |
| 35.0 | 26.8 | 13.00 | 11.00 |
F4FP045 |
| 24 |
| – | 1200 |
| 35.0 | 26.8 | 13.00 | 11.00 | |
|
|
|
| ||||||||
| AHP/SHP48 |
| 21 |
| – | 1400 |
| 41.5 | 31.4 | 13.00 | 11.00 |
THGD42S41S1 |
|
|
|
|
|
|
|
|
|
|
|
F4FP045 |
| 24 |
| – | 1400 |
| 41.0 | 31.2 | 13.00 | 11.00 | |
| F5FP048 |
| 24 |
| – | 1450 |
| 41.0 | 32.6 | 13.00 | 11.00 |
| AHP/SHP60 |
| 24 |
| – | 1600 |
| 47.0 | 36.0 | 14.00 | 11.50 |
THGD48S41S1 |
|
|
|
|
|
|
|
|
|
|
|
F5FP048 |
| 24 |
| – | 1700 |
| 47.5 | 36.6 | 14.00 | 11.50 | |
| F5FP060 |
| 24 |
| – | 1700 |
| 47.5 | 36.8 | 14.00 | 11.50 |
Rated in accordance with DOE test procedures (Federal Register
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in
1.MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
— = Not applicable.
Johnson Controls Unitary Products | 5 |