TABLE 18 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 2,000 CFM (B1HH060)
OUTDOOR |
|
|
|
| INDOOR WB TEMPERATURE, °F |
|
|
|
| ||||
TEMPERATURE, |
|
|
|
|
|
|
|
|
|
|
|
|
|
55 | 57 | 59 | 61 |
| 63 | 65 | 67 |
| 69 | 71 | 73 | 75 | |
°F |
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
65 | — | — | — | 5.4 |
| 6.8 | 8.3 | 9.8 |
| 15.5 | 21.2 | 27.0 | 32.7 |
70 | — | — | — | — |
| 6.3 | 7.8 | 9.2 |
| 14.9 | 20.6 | 26.2 | 31.9 |
75 | — | — | — | — |
| 5.8 | 7.2 | 8.6 |
| 14.2 | 19.9 | 25.5 | 31.1 |
80 | — | — | — | — |
| 5.3 | 6.7 | 8.0 |
| 13.6 | 19.2 | 24.8 | 30.3 |
85 | — | — | — | — |
| — | 6.1 | 7.4 |
| 12.9 | 18.5 | 24.0 | 29.6 |
90 | — | — | — | — |
| — | — | 5.8 |
| 10.5 | 15.3 | 20.0 | 24.8 |
95 | — | — | — | — |
| — | — | — |
| 8.2 | 12.1 | 16.1 | 20.0 |
100 | — | — | — | — |
| — | — | — |
| 6.8 | 10.0 | 13.1 | 16.3 |
105 | — | — | — | — |
| — | — | — |
| 5.5 | 7.8 | 10.2 | 12.5 |
110 | — | — | — | — |
| — | — | — |
| — | 5.7 | 7.2 | 8.8 |
115 | — | — | — | — |
| — | — | — |
| — | — | — | 5.0 |
TABLE 19 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 2,000 CFM (B1HH060)
INDOOR DB |
|
| HEATING SUPERHEAT AT COMPRESSOR SUCTION, °F |
|
| ||||
TEMPERATURE, |
|
|
|
|
|
|
|
| |
0 | 10 | 20 | 30 | 40 | 50 | 60 | |||
°F | |||||||||
|
|
|
|
|
|
|
|
| |
55 | — | — | 2.9 | 3.1 | 3.7 | 5.3 | 9.4 | 20.0 | |
70 | — | — | — | — | — | — | 6.6 | 17.3 | |
80 | — | — | — | — | — | — | — | 10.2 |
Unitary Products Group | 11 |