66297-YIM-C-0205

TABLE 18 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 2,000 CFM (B1HH060)

OUTDOOR

 

 

 

 

INDOOR WB TEMPERATURE, °F

 

 

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

5.4

 

6.8

8.3

9.8

 

15.5

21.2

27.0

32.7

70

 

6.3

7.8

9.2

 

14.9

20.6

26.2

31.9

75

 

5.8

7.2

8.6

 

14.2

19.9

25.5

31.1

80

 

5.3

6.7

8.0

 

13.6

19.2

24.8

30.3

85

 

6.1

7.4

 

12.9

18.5

24.0

29.6

90

 

5.8

 

10.5

15.3

20.0

24.8

95

 

 

8.2

12.1

16.1

20.0

100

 

 

6.8

10.0

13.1

16.3

105

 

 

5.5

7.8

10.2

12.5

110

 

 

5.7

7.2

8.8

115

 

 

5.0

TABLE 19 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 2,000 CFM (B1HH060)

INDOOR DB

 

 

HEATING SUPERHEAT AT COMPRESSOR SUCTION, °F

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

-10

0

10

20

30

40

50

60

°F

 

 

 

 

 

 

 

 

 

55

2.9

3.1

3.7

5.3

9.4

20.0

70

6.6

17.3

80

10.2