York THRU 060, B1HH018 COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,400 CFM B1HH042

Models: B1HH018 THRU 060

1 28
Download 28 pages 53.09 Kb
Page 10
Image 10

66297-YIM-C-0205

TABLE 14 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,400 CFM (B1HH042)

OUTDOOR

 

 

 

 

INDOOR WB TEMPERATURE, °F

 

 

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

19.6

22.0

24.4

26.8

 

29.2

31.6

34.0

 

34.8

35.6

36.4

37.2

70

19.1

21.5

23.9

26.2

 

28.6

31.0

33.3

 

34.2

35.0

35.9

36.7

75

18.7

21.0

23.4

25.7

 

28.0

30.3

32.7

 

33.6

34.5

35.4

36.2

80

18.2

20.5

22.8

25.1

 

27.4

29.7

32.0

 

32.9

33.9

34.8

35.8

85

17.8

20.0

22.3

24.6

 

26.8

29.1

31.3

 

32.3

33.3

34.3

35.3

90

15.5

17.5

19.5

21.5

 

23.5

25.5

27.5

 

29.3

31.0

32.8

34.6

95

13.2

14.9

16.7

18.4

 

20.2

21.9

23.7

 

26.2

28.8

31.3

33.9

100

10.2

11.7

13.3

14.8

 

16.4

17.9

19.5

 

22.4

25.3

28.2

31.2

105

7.2

8.5

9.9

11.2

 

12.6

13.9

15.3

 

18.6

21.9

25.1

28.4

110

5.3

6.5

7.6

 

8.8

9.9

11.1

 

14.7

18.4

22.1

25.7

115

 

5.9

6.9

 

10.9

14.9

19.0

23.0

TABLE 15 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,400 CFM (B1HH042)

INDOOR DB

 

 

HEATING SUPERHEAT AT COMPRESSOR SUCTION, °F

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

-10

0

10

20

30

40

50

60

°F

 

 

 

 

 

 

 

 

 

55

4.0

6.2

9.0

12.5

16.6

70

4.4

7.2

10.7

14.8

80

3.3

7.4

TABLE 16 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,600 CFM (B1HH048)

OUTDOOR

 

 

 

 

INDOOR WB TEMPERATURE, °F

 

 

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

18.5

20.8

23.1

25.4

 

27.7

30.3

32.3

 

33.0

33.8

34.6

35.3

70

15.2

17.4

19.6

21.7

 

23.9

26.1

28.3

 

29.9

31.6

33.2

34.8

75

11.8

13.9

16.0

18.1

 

20.2

22.3

24.3

 

26.8

29.3

31.8

34.3

80

8.5

10.4

12.4

14.4

 

16.4

18.4

20.4

 

23.7

27.1

30.4

33.8

85

5.1

7.0

8.9

10.88

 

12.6

14.5

16.4

 

20.6

24.8

29.0

33.2

90

5.6

6.6

7.6

8.6

 

9.7

10.7

11.7

 

16.4

21.1

25.8

30.5

95

6.1

6.3

6.4

6.5

 

6.7

6.8

7.0

 

12.2

17.3

22.5

27.7

100

5.9

6.0

6.1

6.2

 

6.3

6.4

6.4

 

10.7

14.9

19.1

23.3

105

5.7

5.7

5.8

5.8

 

5.8

5.9

5.9

 

9.2

12.4

15.7

18.9

110

5.5

5.5

5.5

5.4

 

5.4

5.4

5.4

 

7.7

10.0

12.2

14.5

115

5.3

5.2

5.1

5.1

 

5.0

 

6.2

7.5

8.8

10.1

TABLE 17 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,600 CFM (B1HH048)

INDOOR DB

 

 

HEATING SUPERHEAT AT COMPRESSOR SUCTION, °F

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

-10

0

10

20

30

40

50

60

°F

 

 

 

 

 

 

 

 

 

55

3.0

3.5

4.2

5.1

6.5

8.5

11.3

70

3.1

4.5

6.5

9.3

80

4.8

10

Unitary Products Group

Page 10
Image 10
York THRU 060, B1HH018 installation instructions COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,400 CFM B1HH042