York B1HH018, THRU 060 installation instructions Normal Maintenance

Models: B1HH018 THRU 060

1 28
Download 28 pages 53.09 Kb
Page 17
Image 17
MAINTENANCE

66297-YIM-C-0205

TABLE 23 - THERMOSTAT SIGNALS (THREE PHASE UNITS)

SIGNAL

STATE

BOARD FUNCTION

 

 

 

 

 

 

“G”

ON

FAN INSTANT ON

 

 

OFF

FAN INSTANT OFF

 

 

 

 

 

 

FAN INSTANT ON

 

ON

COMPRESSOR AND OUTDOOR FAN INSTANT ON (AFTER ANTI-SHORT CYCLE DELAY)

 

REVERSING VALVE ENERGIZED

“G” & “Y” & “O”

 

 

SYSTEM OPERATES IN COOLING

 

 

 

 

OFF

COMPRESSOR AND OUTDOOR FAN INSTANT OFF

 

FAN 60 SEC. DELAY OFF

 

 

 

 

 

 

 

FAN INSTANT ON

 

ON

COMPRESSOR AND OUTDOOR FAN INSTANT ON (AFTER ANTI-SHORT CYCLE DELAY)

“G” & “Y”

 

SYSTEM OPERATES IN HEATING

 

 

 

OFF

COMPRESSOR AND OUTDOOR FAN INSTANT OFF

 

FAN 60 SEC. DELAY OFF

 

 

 

 

 

 

 

FAN INSTANT ON

 

ON

HEATER BANK 1, 2 & 3 ELEC. HEAT INSTANT ON

“G” & “W”

 

HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON

 

 

 

HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF

 

 

 

OFF

HEATER BANK 1, 2 & 3 ELEC. HEAT ￿￿SEC. DELAY OFF

 

 

FAN 10 SEC. DELAY OFF

 

 

 

 

 

FAN INSTANT ON

 

 

COMPRESSOR AND OUTDOOR FAN INSTANT ON

 

ON

SYSTEM OPERATES IN HEATING

 

 

HEATER BANK 1, 2 & 3 ELEC. HEAT INSTANT ON

“G” & “Y” & “W”

 

HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON

 

 

 

 

COMPRESSOR AND OUTDOOR FAN INSTANT OFF

 

 

HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF

 

OFF

HEATER BANK 1, 2 & 3 ELEC. HEAT ￿￿SEC. DELAY OFF

 

 

FAN 60 SEC. DELAY OFF

 

 

 

 

 

FAN INSTANT ON

 

ON

HEATER BANK 1, 2 & 3 ELEC. HEAT INSTANT ON

“W”

 

HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON

 

 

 

HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF

 

 

 

OFF

HEATER BANK 1, 2 & 3 ELEC. HEAT ￿￿SEC. DELAY OFF

 

 

FAN 10 SEC. DELAY OFF

 

 

MAINTENANCE

NORMAL MAINTENANCE

 

WARNING: Prior to any of the following maintenance proce- dures, shut off all power to the unit, to avoid per- sonal injury.

Periodic maintenance consists of changing or cleaning filters and general cleaning of the outdoor coil.

FILTERS - Inspect once a month. Replace Disposable or clean Permanent Type as necessary. DO NOT replace Per- manent Type with Disposable.

MOTORS - Indoor and outdoor fan motors are permanently lubricated and require no maintenance.

OUTDOOR COIL - Dirt should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit. Cleaning should be as often as necessary to keep the coil clean. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean the coil, be sure that the power to the unit is shut off prior to cleaning.

CAUTION: Exercise care when cleaning the coil so that the coil fins are not damaged.

Do not permit the hot condenser air discharge to be obstructed by overhanging structures or shrubs.