York THRU 060, B1HH018 Typical Field Wiring Diagram, Control Wiring, Power Wiring

Models: B1HH018 THRU 060

1 28
Download 28 pages 53.09 Kb
Page 4
Image 4
CONTROL WIRING

66297-YIM-C-0205

CONTROL WIRING

THERMOSTAT

** = Minimum wire size of 18 AWG

R

wire should be used for all field

G

installed 24 volt wire.

 

 

 

 

Y

 

 

 

W

 

PROGRAMMABLE

 

 

 

THERMOSTAT ONLY

 

 

 

 

 

 

 

UNIT TERMINAL STRIP

**

 

NOTE:

R

HEAT ANTICIPATOR

 

G

SHOULD BE SET AT 0.25

 

AMPS FOR ALL MODELS.

 

 

 

Y

 

*

W2

24 VOLT TRANSFORMER

 

 

W1

 

OO

*= Only required on units with supplemental electric heat.

CC

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

POWER WIRING

REFER TO ELECTRICAL DATA

REFER TO ELECTRICAL DATA

TABLES TO SIZE THE DISCON-

TABLES TO SIZE THE DISCON-

NECT SWITCH, WIRING &

NECT SWITCH, WIRING &

OVERCURRENT PROTECTION.

OVERCURRENT PROTECTION.

 

 

FIG. 2 - TYPICAL FIELD WIRING DIAGRAM

TABLE 3 - PHYSICAL DATA

 

MODELS

 

 

 

BHH

 

 

 

 

018

024

030

036

042

048

060

 

 

INDOOR

CENTRIFUGAL BLOWER (Dia. x Wd. in.)

9 X 6

10 X 8

10 X 8

10 x 8

11 x 10

11 x 10

11 x 10

BLOWER

FAN MOTOR HP (Three Speed)

￿￿

￿￿

￿￿

￿￿

￿￿

￿￿

1

INDOOR

ROWS DEEP

2

2

3

3

3

3

3

FINS PER INCH

15

15

13

15

16

16

16

COIL

FACE AREA (Sq. Ft.)

4.38

4.38

4.38

4.38

5.63

5.63

5.63

 

 

PROPELLER DIA. (in.)

22

22

22

22

22

22

22

OUTDOOR

FAN MOTOR HP

￿￿

￿￿

￿￿

￿￿

￿￿

￿￿

￿￿

FAN

NOM. CFM TOTAL

1,800

1.800

1,800

2,400

2,400

3,000

3,000

 

OUTDOOR

ROWS DEEP

1

1

1

2

2

2

2

FINS PER INCH

20

20

20

20

20

20

20

COIL

FACE AREA (Sq. Ft.)

8.3

11.7

11.7

11.7

16.4

16.4

16.4

 

CHARGE

REFRIGERANT 22 (lbs./oz.)

5 / 6

5 / 5

6 / 5

8 / 12

11 / 8

12 / 0

9 / 0

FILTER

FACE AREA (Sq. Ft. / Qty. / Size)

 

 

4.28 / 2 / 14" x 22"

 

 

COMPRESSOR

HERMETIC Type, (Qty. = 1)

Reciprocating

Reciprocating

Scroll

Scroll

Scroll

Scroll

Scroll

4

Unitary Products Group

Page 4
Image 4
York THRU 060, B1HH018 installation instructions Typical Field Wiring Diagram, Control Wiring, Power Wiring