66297-YIM-C-0205

TABLE 10 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,000 CFM (B1HH030)

OUTDOOR

 

 

 

 

INDOOR WB TEMPERATURE, °F

 

 

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

5.8

10.8

15.8

 

20.8

25.8

30.8

 

31.7

32.6

33.4

34.3

70

5.1

9.3

13.6

 

17.8

22.1

26.3

 

28.0

29.6

31.3

32.9

75

7.9

11.4

 

14.8

18.3

21.8

 

24.2

26.7

29.1

31.6

80

6.4

9.1

 

11.9

14.6

17.3

 

20.5

23.7

27.0

30.2

85

6.9

 

8.9

10.8

12.8

 

16.8

20.8

24.8

28.8

90

 

5.9

7.1

8.3

 

13.1

17.9

22.6

27.4

95

 

 

9.4

14.9

20.5

26.0

100

 

 

7.6

12.0

16.3

20.7

105

 

 

5.9

9.0

12.2

15.3

110

 

 

6.1

8.0

9.9

115

 

 

TABLE 11 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,000 CFM (B1HH030)

INDOOR DB

 

 

HEATING SUPERHEAT AT COMPRESSOR SUCTION, °F

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

-10

0

10

20

30

40

50

60

°F

 

 

 

 

 

 

 

 

 

55

5.8

7.9

9.6

13.4

19.1

26.9

36.6

70

5.4

11.2

18.9

28.7

80

8.1

15.9

25.6

TABLE 12 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,200 CFM (B1HH036)

OUTDOOR

 

 

 

 

INDOOR WB TEMPERATURE, °F

 

 

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

5.2

7.3

9.4

 

11.6

13.7

15.8

 

20.0

24.2

28.4

32.6

70

6.4

8.2

 

10.0

11.8

13.6

 

17.9

22.2

26.5

30.8

75

5.5

6.9

 

8.4

9.8

11.3

 

15.7

20.2

24.6

29.1

80

5.7

 

6.8

7.9

9.1

 

13.6

18.2

22.7

27.3

85

 

5.2

6.0

6.8

 

11.5

16.2

20.8

25.5

90

 

 

9.3

14.2

19.0

23.8

95

 

 

7.2

12.1

17.1

22.0

100

 

 

5.9

9.9

14.0

18.0

105

 

 

7.7

10.9

14.0

110

 

 

5.5

7.8

10.1

115

 

 

6.1

TABLE 13 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,200 CFM (B1HH036)

INDOOR DB

 

 

HEATING SUPERHEAT AT COMPRESSOR SUCTION, °F

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

-10

0

10

20

30

40

50

60

°F

 

 

 

 

 

 

 

 

 

55

3.3

4.1

5.3

7.0

9.5

13.2

70

3.8

5.5

8.0

11.7

80

4.5

8.2

Unitary Products Group

9

Page 9
Image 9
York B1HH018, THRU 060 installation instructions 10.8 15.8