TABLE 21 - ADDITIONAL STATIC PRESSURE RESISTANCE

66297-YIM-C-0205

TABLE 21 - ADDITIONAL STATIC PRESSURE RESISTANCE

 

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

600

700

800

900

1,000

1,100

1,200

1,300

1,400

1,500

1,600

1,700

1,800

1,900

2,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wet Indoor coil

0.01

0.01

0.01

0.02

0.01

0.02

0.03

0.04

0.04

0.03

0.04

0.04

0.05

0.05

0.06

0.07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Economizer

0.00

0.00

0.00

0.01

0.01

0.01

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.07

0.08

0.08

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Filter/Frame Kit

0.01

0.02

0.02

0.02

0.02

0.02

0.03

0.03

0.03

0.03

0.04

0.05

0.05

0.06

0.06

0.07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric Heat

0.02

0.03

0.03

0.03

0.04

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.01

0.11

0.11

0.12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: 1. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2.The pressure thru the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.

CLEARANCES

(Minimum)

Front

12"

Back

0"

Left Side (Filter Access)

24"

Right Side

24"

Below Unit

0"

Above Unit￿

36" (For CondenserAir Discharge)

Units may be installed on combustible floors made from wood or class A, ￿B or C roof covering material.

Units must be installed outdoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

NOTE: FOR UNITS APPLIED WITH A ROOF

 

CURB, THE MINIMUM CLEARANCE MAY BE

￿￿

TERIAL AND THE SUPPLY DUCT.

￿￿￿￿￿￿￿￿￿￿￿￿￿￿

REDUCED FROM 1 INCH TO 1/2 INCH BE-

 

TWEEN COMBUSTIBLE ROOF CURB MA-

 

FIG. 3 - CLEARANCES

Unitary Products Group

13

Page 13