TABLE 5 - ELECTRICAL DATA (12 SEER HEAT PUMP / ELECTRIC HEAT) (Continued)

MODEL BHH

 

COMPRESSOR

COND.

SUPPLY

ELECTRIC HEAT ACCESSORY

 

MAX.

MAX.

 

 

 

 

 

 

 

 

RLA

LRA

MOTOR,

 

KW

 

AMPACITY

 

POWER

 

 

FAN

AIR

 

 

 

MINIMUM

FUSE

HACR2

 

SUPPLY

 

 

MOTOR

BLOWER

MODEL

 

TOTAL

CIRCUIT

SIZE,1

BREAKER

 

 

 

 

FLA

FLA

NO.

 

AMPS

 

AMPS

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

575-3-60

4.7

32.0

0.4

1.5

2NH04501058

10.0***

9.6

19.8

20

20

2NH04501558

15.0***

14.4

25.8

30

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

575-3-60

5.4

34.0

0.4

1.5

2NH04501058

10.0***

9.6

20.7

25

25

2NH04501558

15.0***

14.4

26.7

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501058

10.0***

9.6

20.6

25

25

048

575-3-60

5.1

37.2

0.6

1.6

2NH04501558

15.0***

14.4

26.7

30

30

2NH04502058

20.0***

19.2

32.7

35

35

 

 

 

 

 

 

 

 

 

 

 

 

2NH04502558

25.0***

24.1

38.7

40

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2NH04501058

10.0***

9.6

24.2

25

25

060

575-3-60

7.0

50.0

0.6

2.8

2NH04501558

15.0***

14.4

30.2

35

35

2NP04502058

20.0***

19.2

36.3

40

40

 

 

 

 

 

 

 

 

 

 

 

 

2NP04502558

25.0***

24.1

42.3

45

45

 

 

 

 

 

 

 

 

 

 

 

 

1= Dual element, time delay type.

2= Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.

*= KW listed is for 240 volts, use table on previous page for 208 or 230 volts.