CLEARANCES

All units require certain clearances for proper operation and service. Refer to Figure 3 for the clearances required for com- bustion, construction, servicing and proper unit operation.

WARNING: Do not permit overhanging structures or shrubs to obstruct the condenser air discharge outlet.

DUCT WORK

These units are adaptable to downflow use as well as rear supply and return air duct openings. To convert to downflow, use the following steps:

1.Remove the duct covers found in the bottom return and supply air duct openings. There are four (4) screws secur- ing each duct cover (save these screws to use later).

2.Install the duct covers, removed in step one, to the rear sup- ply and return air duct openings. Secure with the four (4) screws used in step one.

3.Seal duct covers with silicone caulk.

Downflow units must have an “L”-shaped supply duct without any outlets or registers located below the outlet of the unit.

Duct work should be designed and sized according to the methods of the Air Conditioning Contractors of America (ACCA), as set forth in their Manual D.

A closed return duct system shall be used. This shall not pre- clude use of economizers or ventilation air intake. Flexible joints may be used in the supply and return duct work to mini- mize the transmission of noise.

CAUTION: When fastening duct work to the side duct flanges on the unit, insert the screws through the duct flanges only. DO NOT insert the screws through the casing. Outdoor duct work must be insulated and waterproofed.

NOTE: Be sure to note supply and return openings.

Refer to Figure 4 for information concerning rear and bottom supply and return air duct openings.

FILTERS

Single phase units are shipped without a filter and is the re- sponsibility of the installer to secure a filter in the return air

ductwork or install a Filter/Frame Kit (1FF0114).

A filter rack and a high velocity filters are standard on three phase units.

Filters must always be used and must be kept clean. When filters become dirt laden, insufficient air is delivered by the blower, decreasing your unit's efficiency and increasing oper- ating costs and wear-and-tear on the unit and controls.

Filters should be checked monthly especially since this unit is used for both heating and cooling.

CONDENSATE DRAIN

A condensate trap is required to be installed in the conden- sate drain. The plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install the conden- sate drain line (￿CLEARANCES￿" NPTF) to spill into an open drain.

SERVICE ACCESS

Access to all serviceable components is provided by the follow- ing removable panels:

Blower service access

Electrical/Filter access

Compressor service access

Refer to Figure 3 for location of these access panels and mini- mum clearances.

THERMOSTAT

The room thermostat should be located on an inside wall ap- proximately 56" above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appli- ances. Follow manufacturer's instructions enclosed with the thermostat for general installation procedure. Six color coded insulated wires (minimum #18 AWG) should be used to con- nect thermostat to unit. See Figure 2.

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of the cur- rent N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordi- nances. The unit must be electrically grounded in accordance with local codes or, in their absence, with the N.E.C./C.E.C. Voltage tolerances which must be maintained at the compressor terminals during starting and running con- ditions are indicated on the unit Rating Plate and Table 3.

The wiring entering the cabinet must be provided with me- chanical strain relief.

A fused disconnect switch should be field provided for the unit. If any of the wire supplied with the unit must be replaced, replace- ment wire must be of the type shown on the wiring diagram.

Electrical line must be sized properly to carry the load. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.

Refer to Figure 2 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information.

COMPRESSORS

Units are shipped with compressor mountings factory- adjusted and ready for operation.

CAUTION: Do Not loosen compressor mounting bolts.