Physical Data - (English Units)
|
|
|
|
| Model Number YCUL |
|
|
| |
| 0016 | 0026 | 0030 | 0036 | 0040 | 0046 | 0050 | 0056 | 0060 |
General Unit Data |
|
|
|
|
|
|
|
|
|
Nominal Tons, | 15.2 | 20.8 | 25.9 | 31.2 | 37.7 | 42.3 | 46.9 | 51.7 | 56.2 |
Nominal Tons, | 14.5 | 20.1 | 25.1 | 30.7 | 36.6 | 40.9 | 45.5 | 50.2 | 54.9 |
Number of Refrigerant Circuits | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 |
Refrigerant Charge, Operating |
|
|
|
|
|
|
|
|
|
25.0 | 29.6 | 45.2 | 50.7 | 53.8 | 35.1/35.1 | 42.1/35.1 | 42.1/42.1 | 46.8/42.1 | |
24.1 | 28.5 | 43.6 | 48.9 | 51.9 | 33.8/33.8 | 40.6/33.8 | 40.6/40.6 | 45.1/40.6 | |
Pumpdown Capacity |
|
|
|
|
|
|
|
|
|
43.2 | 43.2 | 60.5 | 90.7 | 90.7 | 58.4/58.4 | 58.4/58.4 | 58.4/58.4 | 58.4/58.4 | |
41.6 | 41.6 | 58.3 | 87.4 | 87.4 | 56.5/56.5 | 56.5/56.5 | 56.5/56.5 | 56.5/56.5 | |
Oil Charge, ckt1 / ckt2, gallons | 2.2 | 2.2 | 2.2 | 2.2 | 3.3 | 2.2/2.2 | 2.2/2.2 | 2.2/2.2 | 2.2/2.2 |
Operating / Shipping Weight |
|
|
|
|
|
|
|
|
|
Aluminum Fin Coils, lbs | 2051 | 2058 | 2401 | 2445 | 2788 | 3947 | 4000 | 4057 | 4114 |
Copper Fin Coils, lbs | 2201 | 2208 | 2551 | 2595 | 2938 | 4247 | 4300 | 4357 | 4414 |
Compressors, scroll type |
|
|
|
|
|
|
|
|
|
Compressors per circuit | 2 | 2 | 2 | 2 | 3 | 2 | 2 | 2 | 2 |
Compressors per unit | 2 | 2 | 2 | 2 | 3 | 4 | 4 | 4 | 4 |
Nominal Tons per compressor | 7.5 | 10 | 13 | 15 | 13 | 10/10 | 13/10 | 13/13 | 15/13 |
Condenser |
|
|
|
|
|
|
|
|
|
Total Face Area ft2 | 47.2 | 47.2 | 66.1 | 66.1 | 66.1 | 128.0 | 128.0 | 128.0 | 128.0 |
Number of Rows | 2 | 2 | 2 | 3 | 3 | 2 | 2 | 2 | 2 |
Fins per Inch | 13 | 13 | 13 | 13 | 13 | 13 | 13 | 13 | 13 |
Condenser Fans |
|
|
|
|
|
|
|
|
|
Number of Fans total | 2 | 2 | 2 | 2 | 2 | 4 | 4 | 4 | 4 |
Fan hp/kw | 2 / 1.4 | 2 / 1.4 | 2 / 1.4 | 2 / 1.4 | 2 / 1.4 | 2 / 1.4 | 2 / 1.4 | 2 / 1.4 | 2 / 1.4 |
Fan RPM | 1140 | 1140 | 1140 | 1140 | 1140 | 1140 | 1140 | 1140 | 1140 |
Number of Blades | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 |
Total Chiller CFM | 16257 | 16257 | 23500 | 23500 | 23500 | 47360 | 47360 | 47360 | 47360 |
Notes:
1.Pump Down Capacity is based on 100°F (37.8°C) liquid R22 and 80% of condenser volume.
2.Operating Refrigerant Charge is for Condensing Unit only, does not include refrigerant lines and evaporator coil.
58 | YORK INTERNATIONAL |