FORM 150.63-EG1

MILLENNIUM CONTROL CENTER

All controls are contained in a NEMA 3R/12 (and equivalent to IP55*) cabinet with hinged outer door and includes:

Liquid Crystal Display with Light Emitting Diode backlighting for outdoor viewing:

Two display lines

Twenty characters per line

Color coded 12-button non-tactile keypad with sections for:

DISPLAY/PRINT of typical information: Suction temperatures (optional) Ambient temperature

System pressures (each circuit)

Operating hours and starts (each compressor)

Print calls up to the liquid crystal display: Operating data for the systems History of fault shutdown data for up to the last six fault shutdown conditions

An RS-232 port, in conjunction with this press-to-print button, is provided to permit

the capability of hard copy print-outs via a separate printer (by others).

ENTRY section to:

ENTER setpoints or modify system values

SETPOINTS updating can be performed to: Suction pressure setting

Suction pressure control zone Remote reset temperature range

Set daily schedule/holiday for start/stop Manual override for servicing

Low and high ambient cutouts Number of compressors Low suction pressure cutout High discharge pressure cutout

Anti-recycle timer (compressor start cycle time) Anti-coincident timer (delay compressor starts)

UNIT section to:

Set clock

Set options

Set unit option

Set unit control for Discharge Air Temperature Control or for Suction Pressure Control (requires Suction Pressure Transducers – standard on

YCUL 0076 - 0130 and optional on YCUL0016 - 0066.

UNIT ON/OFF switch

The microprocessor control center is capable of displaying the following:

Suction temperatures (optional)

Low ambient temperature cutout setting

Outdoor air temperature

English or Metric data

Suction pressure cutout setting

Each system suction pressure (optional on 0016

-0066 models and standard on 0076 - 0130 models)

System discharge pressure (optional on 0016 - 0090 models and standard on 0096 - 0130 models)

Discharge Air Temperature Reset via a YORK ISN DDC or Building Automation System (by others) via:

-a pulse width modulated (PWM) input as stan- dard

-a 4-20 milliamp or 0 -10 VDC input, or contact closure with the optional B.A.S. interface option

Anti-recycle timer status for each system

Anti-coincident system start timer condition

Compressor run status

No cooling load condition

Day, date and time

Daily start/stop times

Holiday status

Automatic or manual system lead/lag control (Discharge Air Temperature control only)

Automatic lead/lag of compressors within a system

Compressor starts & operating hours (each compressor)

Status of hot gas valves, and fan operation

Run permissive status

Number of compressors running

Liquid solenoid valve status

Load & unload timer status

YORK INTERNATIONAL

5

Page 5
Image 5
York YCUL0016, YCUL0130 manual Millennium Control Center, Unit ON/OFF switch