York YCUL0016, YCUL0130 manual FORM 150.63-EG1

Models: YCUL0016 YCUL0130

1 124
Download 124 pages 41.63 Kb
Page 57
Image 57
Manual background

FORM 150.63-EG1

YCUL0096EB

%

AMBIENT

 

KW

 

COMPR

COP

DISPL.

DEG C

 

 

kW

 

 

 

 

100.0

35.0

 

306.8

 

90.4

3.03

77.8

29.2

 

253.0

 

61.3

3.60

50.0

20.4

 

172.4

 

34.5

4.52

27.8

12.8

 

99.3

 

16.2

5.53

 

 

 

 

 

 

 

YCUL0106EB

 

 

%

AMBIENT

 

KW

 

COMPR

COP

DISPL.

DEG C

 

 

kW

 

 

 

 

100.0

35.0

 

366.6

 

116.0

2.89

81.8

30.8

 

320.7

 

82.8

3.43

59.1

24.5

 

251.5

 

50.9

4.20

40.9

17.8

 

176.9

 

32.0

4.97

18.2

12.8

 

84.6

 

12.7

5.84

 

 

 

 

 

 

 

YCUL0130EB

 

 

%

AMBIENT

 

KW

 

COMPR

COP

DISPL.

DEG C

 

 

kW

 

 

 

 

100.0

35.0

 

450.3

 

140.4

2.91

85.2

31.4

 

401.5

 

108.6

3.26

66.7

25.7

 

325.3

 

79.3

3.76

51.9

21.0

 

261.4

 

55.6

4.28

33.3

15.0

 

179.6

 

30.2

5.32

18.5

12.8

 

98.7

 

15.8

5.60

YCUL0100EB

%

AMBIENT

 

KW

 

COMPR

COP

DISPL.

DEG C

 

 

kW

 

 

 

 

100.0

35.0

 

331.2

 

99.5

3.00

75.0

28.6

 

267.6

 

64.3

3.65

50.0

20.3

 

185.1

 

38.2

4.43

25.0

12.8

 

99.3

 

16.2

5.53

 

 

 

 

 

 

 

 

 

YCUL0120EB

 

 

%

AMBIENT

 

KW

 

COMPR

COP

DISPL.

DEG C

 

 

kW

 

 

 

 

100.0

35.0

 

413.7

 

125.8

2.95

83.3

31.1

 

365.3

 

94.1

3.37

66.7

25.9

 

300.3

 

70.3

3.87

50.0

20.7

 

236.4

 

47.1

4.50

33.3

15.0

 

165.1

 

26.9

5.40

16.7

12.8

 

84.0

 

12.8

5.76

YORK INTERNATIONAL

57