York YCUL0130, YCUL0016 manual Part Load Ratings - HFC-407CSI Units

Models: YCUL0016 YCUL0130

1 124
Download 124 pages 41.63 Kb
Page 56
Image 56
Part Load Ratings - HFC-407C (SI Units)

Part Load Ratings - HFC-407C (SI Units)

YCUL0016EB

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

51.1

 

14.9

2.89

50.0

21.2

 

29.9

 

5.1

4.57

 

 

 

 

 

 

 

YCUL0030EB

 

 

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

88.4

 

26.9

2.98

50.0

21.2

 

51.7

 

9.6

4.71

 

 

 

 

 

 

 

YCUL0040EB

 

 

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

128.8

 

42.3

2.86

66.7

27.1

 

98.1

 

21.6

4.02

33.3

15.8

 

54.5

 

8.6

5.45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YCUL0050EB

 

 

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

160.0

 

49.1

2.93

78.2

29.4

 

133.1

 

33.1

3.44

50.0

21.1

 

93.4

 

17.2

4.66

28.2

13.1

 

54.9

 

8.8

5.38

 

 

 

 

 

 

 

YCUL0060EB

 

 

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

193.1

 

62.7

2.83

76.5

29.5

 

161.3

 

42.1

3.38

50.0

21.2

 

113.0

 

22.0

4.56

26.5

13.1

 

66.4

 

10.2

5.74

 

 

 

 

 

 

 

YCUL0076EB

 

 

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

234.0

 

76.8

2.80

85.5

31.5

 

209.4

 

59.2

3.17

66.7

27.0

 

177.7

 

39.0

3.88

52.2

21.5

 

139.1

 

29.5

4.23

33.3

15.8

 

99.1

 

15.0

5.39

18.8

12.8

 

55.7

 

8.5

5.48

 

 

 

 

 

 

 

YCUL0086EB

 

 

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

287.6

 

93.4

2.87

84.3

31.5

 

257.6

 

71.9

3.27

66.7

26.9

 

218.1

 

47.4

4.03

51.0

21.3

 

169.2

 

36.5

4.25

33.3

15.7

 

120.9

 

18.2

5.60

17.7

12.8

 

68.0

 

9.0

6.35

YCUL0026EB

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

70.7

 

21.8

2.88

50.0

21.3

 

41.5

 

7.5

4.68

 

 

 

 

 

 

 

YCUL0036EB

 

 

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

108.0

 

32.8

3.04

50.0

21.0

 

62.5

 

11.4

4.89

 

 

 

 

 

 

 

YCUL0046EB

 

 

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

144.0

 

41.4

3.07

75.0

28.6

 

116.5

 

26.3

3.65

50.0

21.0

 

83.7

 

14.3

4.90

25.0

12.8

 

44.9

 

6.0

6.05

 

 

 

 

 

 

 

YCUL0056EB

 

 

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

176.5

 

55.0

2.91

75.0

28.9

 

144.3

 

34.8

3.57

50.0

21.2

 

103.4

 

19.6

4.62

25.0

12.8

 

55.6

 

8.7

5.51

 

 

 

 

 

 

 

YCUL0066EB

 

 

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

215.7

 

65.1

3.05

75.0

28.8

 

175.5

 

40.9

3.77

50.0

20.9

 

124.6

 

22.7

4.88

25.0

12.8

 

67.0

 

9.5

6.16

 

 

 

 

 

 

 

YCUL0080EB

 

 

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

263.3

 

84.0

2.90

83.3

31.2

 

233.0

 

62.3

3.37

66.7

26.9

 

199.2

 

43.2

3.98

50.0

21.0

 

152.3

 

30.9

4.44

33.3

15.6

 

110.2

 

17.4

5.29

16.7

12.8

 

56.3

 

8.5

5.51

 

 

 

 

 

 

 

YCUL0090EB

 

 

%

AMBIENT

 

TONS

 

COMPR

EER

DISPL.

DEG F

 

 

kW

 

 

 

 

100.0

35.0

 

311.2

 

103.5

2.82

83.3

31.2

 

275.9

 

76.2

3.32

66.7

27.0

 

236.5

 

51.9

4.03

50.0

20.8

 

179.1

 

37.5

4.38

33.3

15.7

 

131.2

 

19.1

5.83

16.7

12.8

 

67.3

 

8.9

6.33

56

YORK INTERNATIONAL

Page 56
Image 56
York YCUL0130, YCUL0016 manual Part Load Ratings - HFC-407CSI Units