Design Parameters
ENGLISH UNITS
| SUCTION |
| AIR ON | ||
YCUL | TEMPERATURE (°F) | CONDENSER (°F) | |||
| MIN1 | MAX1 | MIN2 |
| MAX3 |
0016 | 35 | 55 | 0 |
| 125 |
0026 | 35 | 55 | 0 |
| 125 |
0030 | 35 | 55 | 0 |
| 125 |
0036 | 35 | 55 | 0 |
| 125 |
0040 | 35 | 55 | 0 |
| 125 |
0046 | 35 | 55 | 0 |
| 125 |
0050 | 35 | 55 | 0 |
| 125 |
0056 | 35 | 55 | 0 |
| 125 |
0060 | 35 | 55 | 0 |
| 125 |
0066 | 35 | 55 | 0 |
| 125 |
0076 | 35 | 55 | 0 |
| 125 |
0080 | 35 | 55 | 0 |
| 125 |
0086 | 35 | 55 | 0 |
| 125 |
0090 | 35 | 55 | 0 |
| 125 |
0096 | 35 | 55 | 0 |
| 125 |
0100 | 35 | 55 | 0 |
| 125 |
0106 | 35 | 55 | 0 |
| 125 |
0120 | 35 | 55 | 0 |
| 125 |
0130 | 35 | 55 | 0 |
| 125 |
NOTES:
1.For lower or higher suction temperature applications, contact your nearest YORK Office for application requirements.
2.For operation at temperatures below 25°F
-0090 models only).
3.For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.
16 | YORK INTERNATIONAL |