Selection Data
FORM
The ratings shown on pages 18 through 57 are based on unit operation in a well designed and properly piped system.
SELECTION RULES
1.Capabilities are based on Refrigerant 22 or 407C.
2.Ratings may interpolated, but must not be extrapo- lated.
3.Ratings shown are at saturated suction temperatures corresponding to pressures at the compressor. In actual practice, suction line pressure drop has the effect of reducing compressor capacity, forcing the compressor to operate at a lower suction pressure to maintain the desired evaporator temperature.
For normal air conditioning applications, size the suction line for a pressure drop of 3 PSI, corresponding to 2°F, for
SELECTION PROCEDURE
The
allows for normal suction line loss.
If more accurate selection is required, the evaporator capacity should be plotted against the condensing unit capacity to determine the balanced system performance. Again, it is necessary to factor in the suction line loss.
After the system balance point has been determined, the compressor KW input may be interpolated from the ratings tables.
SAMPLE SELECTION
Select an
Design Conditions
1.An air handling unit with four large DX coils (two per circuit) having a total cooling load of 600 MBH (50 tons).
2.The coil suction temperature required 45°F.
3.The design outdoor ambient temperature is 90°F.
4.The power supply is 460V/3 phase/60 HZ.
Selection
1.Enter the YCUL 60 HZ Rating Table (page 20).
2.The model YCUL0056EC will provide 51.3 tons with 48.3 compressor KW input at 90°F ambient air and 43°F suction pressure.
3.Calculate the compressor KW input for the specific design conditions of 50 tons and 90°F ambient air.
50tons
KW = 51.3 tons x 48.3 KW = 47.1 KW
The YCUL0056EC is the suitable selection for the design capacity.
YORK INTERNATIONAL | 9 |