Electrical Notes
NOTES:
I . Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article
2.5 amps;
2.Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit to avoid nuisance trips at
3.Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 440.
4.The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included
in the circuit, per N.E.C. Article 440.
5.Circuit breakers must be UL listed and CSA certified and maximum size is based on 225% of the rated loadamps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Exception: YCUL0016 and YCUL0026 must have the optional factory overloads installed to use a standard circuit breaker. Otherwise, an
6.The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per phase of the wire range specified. Actual wire size and number of wires per phase must be determined based on the National Electrical Code, USING COPPER CONNECTORS ONLY. Field wiring must also comply with local codes.
7.A ground lug is provided for each compressor system to accommodate a field grounding conductor per N.E.C. Table
8.The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100, and is intended for isolating the unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
9.Field Wiring by others which complies to the National Electrical Code & Local Codes.
LEGEND | ACROSS THE LINE START | VOLTAGE CODE | |
C.B. | CIRCUIT BREAKER | ||
D.E. | DUAL ELEMENT FUSE | ||
DISC SW | DISCONNECT SWITCH | ||
FACT MOUNT CB | FACTORY MOUNTED CIRCUIT BREAKER | ||
FLA | FULL LOAD AMPS | ||
HZ | HERTZ |
| |
MAX | MAXIMUM |
| |
MCA | MINIMUM CIRCUIT AMPACITY |
| |
MIN | MINIMUM |
| |
MIN NF | MINIMUM NON FUSED |
| |
RLA | RATED LOAD AMPS |
| |
S.P. WIRE | SINGLE POINT WIRING |
| |
UNIT MTD SERV SW | UNIT MOUNTED SERVICE | ||
LRA | LOCKED ROTOR ARMS |
|
102 | YORK INTERNATIONAL |