York YCUL0130, YCUL0016 manual Electrical Notes, Legend, Voltage Code

Models: YCUL0016 YCUL0130

1 124
Download 124 pages 41.63 Kb
Page 102
Image 102
Electrical Notes

Electrical Notes

NOTES:

I . Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the optional Factory Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system providing power to the transformer: -17, add

2.5 amps; -28, add 2.3 amps; -40, add 1.5 amps, -46, add 1.3 amps; -58, add 1 amps.

2.Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It is not recommended in applications where brown outs, frequent starting and stopping of the unit, and/or operation at ambient temperatures in excess of 95ºF (35ºC) is anticipated.

3.Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 440.

4.The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included

in the circuit, per N.E.C. Article 440.

5.Circuit breakers must be UL listed and CSA certified and maximum size is based on 225% of the rated loadamps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Exception: YCUL0016 and YCUL0026 must have the optional factory overloads installed to use a standard circuit breaker. Otherwise, an HACR-type circuit breakers must be used. Maximum HACR circuit breaker rating is based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit.

6.The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per phase of the wire range specified. Actual wire size and number of wires per phase must be determined based on the National Electrical Code, USING COPPER CONNECTORS ONLY. Field wiring must also comply with local codes.

7.A ground lug is provided for each compressor system to accommodate a field grounding conductor per N.E.C. Table 250-95. A control circuit grounding lug is also supplied.

8.The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100, and is intended for isolating the unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.

9.Field Wiring by others which complies to the National Electrical Code & Local Codes.

LEGEND

ACROSS THE LINE START

VOLTAGE CODE

ACR-LINE

-17 = 200-3-60

C.B.

CIRCUIT BREAKER

-28 = 230-3-60

D.E.

DUAL ELEMENT FUSE

-40 = 380-3-60

DISC SW

DISCONNECT SWITCH

-46 = 460-3-60

FACT MOUNT CB

FACTORY MOUNTED CIRCUIT BREAKER

-58 = 575-3-60

FLA

FULL LOAD AMPS

HZ

HERTZ

 

MAX

MAXIMUM

 

MCA

MINIMUM CIRCUIT AMPACITY

 

MIN

MINIMUM

 

MIN NF

MINIMUM NON FUSED

 

RLA

RATED LOAD AMPS

 

S.P. WIRE

SINGLE POINT WIRING

 

UNIT MTD SERV SW

UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT SWITCH)

LRA

LOCKED ROTOR ARMS

 

102

YORK INTERNATIONAL

Page 102
Image 102
York YCUL0130, YCUL0016 manual Electrical Notes, Legend, Voltage Code