VOYAGEUR GRAND Wood Insert
Masonry Chimney (Cont’d)
This insert conforms with the UL 1482 and ULC S628 (Canada) in all respects, and is approved to UL & ULC safety standards for installation and use within a fireplace with a masonry chimney in accordance with NFPA 211 and
In USA a minimum 5 foot length, 6 inch diameter flue liner is required as per UL 1482, however Hearth & Home Technologies strongly recommends a full reline for optimum performance.
NOTE: In Canada, this fireplace insert must be installed with a continuous chimney liner of a 6 inch (152mm) diam- eter extending from the fireplace insert to the the top of the chimney.
The chimney liner must conform to the Class 3 require- ments of
UL 1777 Insulated Stainless Steel Liner or Other Approved Lining System
Follow Manufacturer’s Instructions on Insulation and Support
For Zero or Other
Masonry Chimney Must
Have Structural Integrity
UL 1777 Insulated Stainless Steel
Liner or Other Approved Lining System
Minimum 8 in. (203mm) Masonry
Thickness in Front of Smoke Chamber
Minimum Clearance in Accordance with Insert Listing
Floor Protection in
Accordance with Insert
Listing
Combustible Floor
Follow Manufacturer’s
Instructions for Maximum
Liner Extension Above
Chimney
Maximum 30 Degrees
Offset in Chimney
Damper Plate Removed or
Fastened in Open Position
Seal with
NOTE: Generic wood insert shown - not model specific
Figure 35.1 - Masonry Chimney with a Full Liner Kit Type UL103HT Rquirement per UL1777
September 25, 2012 | Page 35 |