Radware VOYA-GRAND-MBK, VOYA-GRAND-PMH Voyageur Grand Wood Insert Metal Heat Circulating Masonry

Page 36

VOYAGEUR GRAND Wood Insert

R

E. Metal Heat Circulating Masonry

This insert conforms with the safety standard UL-1482 and ULC S628 (Canada) in all respects and is approved to UL & ULC safety standards for installation and use within a fire- place with masonry chimney, in accordance with NFPA 211, and CAN/CSA-B365-01.

F. Prefabricated Metal Chimney

The chimney can be new or existing, masonry or prefabricated and must meet the following minimum requirements:

•Must be minimum 6 inch (152mm) inside diameter of high temperature chimney listed to UL 103 HT (2100oF) or ULC S628.

•Must use components required by the manufacturer for installation.

•Must maintain clearances required by the manufacturer for installation.

•Refer to manufacturers instructions for installation

•This insert is listed to UL 1482 Standard and is approved for installation into listed factory-built solid fuel fireplaces listed to UL 127 conforming to the follow- ing specifications and instructions:

•The original factory-built clearance fireplace chimney cap must be re-installed after installing the approved chimney liner meeting type UL 103 HT requirements (2100°F) per UL 1777.

•The liner must be securely attached to the insert flue collar and the chimney top.

•The air flow of the factory-built solid fuel fireplace system must not be altered. The flue liner top support attachment must not reduce the air flow for the existing air-cooled chimney system.

•No dilution air is allowed to enter the chimney.

1.Secure the fireplace damper in the open position.

If this cannot be accomplished, it will be necessary to remove the damper.

2.Seal damper area of chimney around chimney connector with a high temperature sealant or seal insert against the face of the fireplace.

3.Both methods must be removable and replaceable for cleaning and re-installation.

 

Inches

Millimeters

Minimum Width of Cavity Opening - Front

32-7/8*

835

Minimum Width of Cavity Opening - Rear

24*

610

Minimum Height

24*

610

Minimum Depth from Front to Rear

18*

457

*You will need to add additional clearances to these dimensions for your specific installation. Also allow suf- ficient clearance if you are installing an outside air kit.

NOTE: Refer to chimney liner manufacturer for recom- mendations on supporting the liner. Installation into fireplaces without a permit will void the listing.

NOTICE: In Canada when using a factory-built chimney it must be safety listed, Type UL103 HT (2100oF) [1149oC] CLASS “A” or conforming to CAN/ULC-S629M, STANDARD FOR 650oC FACTORY-BUILT CHIMNEYS.

WARNING

Fire Risk.

When lining air-cooled factory-built chimneys:.

Run chimney liner approved to UL 1777 Type HT requirements (2100 degrees F)

Re-install original factory built chimney cap

ONLY

DO NOT block cooling air openings in chimney

Blocking cooling air will overheat the chimney

To maintain the functionality of the fireplace’s chimney system you may use a Simpson Dura-Vent DuraLiner Slip Hanger, Part # 4671, and attach to the bottom of the fireplace chimney cap to support the liner. You have two options to completing the installation.

Option one - Not required to use liner cap: Re-attach the existing top of the chimney cap.

Option two - Using liner cap:

Re-attach the existing top of the chimney cap and install a new storm collar and a new liner cap.

WARNING! Risk of Fire!

Follow venting manufacturer’s clearances and instructions when installing venting system.

Page 36

7075-166

September 25, 2012

Image 36
Contents Voyageur Grand Wood Insert Hot glass will cause burnsVoyageur Grand Wood Insert Welcome to the Quadra-Fire FamilyTable of Contents Limited Lifetime Warranty Warranty Conditions BTU & Efficiency Specifications Glass SpecificationsListing and Code Approvals Appliance CertificationOperating Instructions Your Wood ApplianceGeneral Operating Parts Voyageur Grand Wood Insert Fire Safety Combustible/Non-combustible MaterialsOverfiring Seasoned WoodVoyageur Grand Wood Insert Burning Process Kindling or First StageSecond Stage Final StageVoyageur Grand Wood Insert Automatic Combustion Control ACC Air ControlsBurn Rates and Operating Efficiency Incorrect Positions Voyageur Grand Wood Insert Building a Fire Fuel Reloading InstructionsWood Fuel MoistureBlower Operating Instructions Frequently Asked Questions Voyageur Grand Wood Insert Clear SpaceOpacity Smoke Voyageur Grand Wood Insert Quick Start Guide Your specific modelMaintenance and Service Chimney and Chimney Connector Inspection/CleaningCleaning Plated Surfaces Disposal of AshesVoyageur Grand Wood Insert Glass Cleaning Inspect Firebrick & Replacement InstructionsVoyageur Grand Wood Insert Quick Reference Maintenance Guide Troubleshooting Guide Start Fire Problems Possible Cause SolutionService Parts Replacement Glass ReplacementSnap Disc Replacement Contd Snap Disc ReplacementVoyageur Grand Wood Insert Blower Replacement Shock RiskVoyageur Grand Wood Insert Door Handle Assembly Baffle & Ceramic Blanket Removal51mm. Figure Voyageur Grand Wood Insert Tube Channel Assembly Replacement Design and Installation Considerations Getting StartedDraft Voyageur Grand Wood Insert Negative Pressure Voyageur Grand Wood Insert Locating Your Stove & Chimney Chimney Termination RequirementsVoyageur Grand Wood Insert Rule Voyageur Grand Wood Insert Tools And Supplies Needed Inspect Appliance and ComponentsPre-Burn Check List Dimensions and Clearances Appliance DimensionsWall Clear of Ashes Thermal Conductivity k value Thermal Resistance R valueConverting k to R Converting R to kChimney Systems Venting SystemsInspections Larger ChimneysVoyageur Grand Wood Insert Masonry Chimney Cont’d Voyageur Grand Wood Insert Metal Heat Circulating Masonry Prefabricated Metal ChimneyVoyageur Grand Wood Insert Securing Chimney Components Altering the FireplaceFactory-Built Sold Fuel Fireplace Chimney Height / Rise and Run Outside Air Kit Installation Items Needed for Installation not suppliedOption One Outside Air Installation Instructions Option Two Outside Air Installation InstructionsLeveling Legs Flue Adapter VerticalDegree Standard Surround & Trim Kit Installation Voyageur Grand Wood Insert Standard Surround & Cast Trim Kit 42.1Blower Cord Installation on Left Side Voyageur Grand Wood Insert All Cast Surround KitPlacement Slot Blower Access Assembly White Wire Mobile Home Installation Service Parts Part number list on followingCast Iron Wood Insert Large #10 Brick Assembly StockedAt Depot #7 Baffle Protection Channel#13 Door Assembly Description Comments Part Number#14 Access Assembly #17 Control Asembly #25 & 26 Surround AssembliesVoyageur Grand Wood Insert Service And Maintenance Log Date of Service Performed By Description of ServiceVoyageur Grand Wood Insert Service And Maintenance Log Voyageur Grand Wood Insert Homeowner’s Notes Contact Information