Radware VOYA-GRAND-PMH, VOYA-GRAND-MBK Voyageur Grand Wood Insert Securing Chimney Components

Page 37
250250-2061-2061

R

VOYAGEUR GRAND Wood Insert

G. Securing Chimney Components

All joints should be secured with 3 sheet metal screws or rivets per pipe manufacturers instructions. The sections must be attached to the insert and to each other with the crimped (male) end pointing toward the insert. Figure 37.1.

LINER CONNECTOR

CRIMPED

FLUE

END

GAS

TOWARDS

DIRECTION

STOVE

 

Figure 37.1

H. Altering the Fireplace

The following modifications of factory-built fireplaces are permissible:

The following parts may be removed:

Damper

Smoke Shelf or Baffle

Ember Catches

Fire Grate

Viewing Screen/Curtain

Doors

The fireplace must not be altered, except that the damper may be removed to accommodate a direct-connect starter pipe or chimney liner,

External trim pieces which do not affect the operation of the fireplace may be removed providing they can be stored on or within the fireplace for reassembly if the insert is removed.

The permanent metal warning label provided in the component pack must be attached to the back of the fireplace, with screws or nails, stating that the fireplace may have been altered to accommodate the insert, and must be returned to original condition for use as a conventional fireplace. Figure 37.2.

Manufacturer designed adjustable support kit can be ordered from your dealer.

Final approval of this installation type is contingent upon the authority having jurisdiction.

WARNING

THIS FIREPLACE MAY HAVE BEEN ALTERED

TO ACCOMMODATE AN INSERT. IT MUST BE

RETURNED TO ITS ORIGINAL CONDITION

BEFORE USE AS A SOLID FUEL BURNING

FIREPLACE.

Figure 37.2

I. Factory-Built Sold Fuel Fireplace

A permit may be required for installations, final approval is contingent of the authority having local jurisdiction. Consult insurance carrier, local building, fire officials or authorities having jurisdiction about restrictions, installation inspec- tion, and permits.

Inspect the existing fireplace and chimney for any damage or flaws such as burnouts, metal or refectory warping.

Inspection to a minimum of NFPA 211 Level II is recom- mended. All repairs must be made prior to installing an insert. The fireplace must be structurally sound and be able to support the weight of the solid-fuel insert

The factory-built chimney must be listed per UL 127 or ULC 610-M87 for all installations. Install thermal protection per this appliance listing requirements.

A full height 6 inch diameter stainless steel full height listed chimney liner must be installed meeting type HT (2100°F) requirements per UL 1777 (USA) or ULC S635 with “0” clearance to masonry (Canada). The full liner must be attached to the insert flue collar and to the top of the existing chimney.

The flue liner top support attachment must not reduce the air flow for the existing air-cooled chimney system. Re- install original factory-built chimney cap only. (See Sec- tion F., Prefabricated Metal Chimney)

To prevent room air passage to the chimney cavity of the fireplace, seal either the damper area around the chimney liner or the insert surround. Circulating air chamber (i.e. in a steel fireplace liner or metal hearth circulator) may not be blocked. The air flow within and around the fireplace shall not be altered, blocked by the installation of the insert. (i.e. no louvers or cooling air inlet or outlet ports may be blocked by the insert or the insert surround.

See “H. Altering the Fireplace” for modifications allowed for factory-built fireplaces.

WARNING! Risk of Asphyxiation!

DO NOT CONNECT THIS APPLIANCE TO A CHIMNEY FLUE SERVICING ANOTHER APPLIANCE OR TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.

This may allow flue gases to enter the house.

September 25, 2012

7075-166

Page 37

Image 37
Contents Hot glass will cause burns Voyageur Grand Wood InsertWelcome to the Quadra-Fire Family Voyageur Grand Wood InsertTable of Contents Limited Lifetime Warranty Warranty Conditions Glass Specifications BTU & Efficiency SpecificationsListing and Code Approvals Appliance CertificationYour Wood Appliance Operating InstructionsGeneral Operating Parts Combustible/Non-combustible Materials Voyageur Grand Wood Insert Fire SafetyOverfiring Seasoned WoodKindling or First Stage Voyageur Grand Wood Insert Burning ProcessSecond Stage Final StageAir Controls Voyageur Grand Wood Insert Automatic Combustion Control ACCBurn Rates and Operating Efficiency Incorrect Positions Fuel Reloading Instructions Voyageur Grand Wood Insert Building a FireMoisture Wood FuelBlower Operating Instructions Voyageur Grand Wood Insert Clear Space Frequently Asked QuestionsOpacity Smoke Your specific model Voyageur Grand Wood Insert Quick Start GuideChimney and Chimney Connector Inspection/Cleaning Maintenance and ServiceCleaning Plated Surfaces Disposal of AshesInspect Firebrick & Replacement Instructions Voyageur Grand Wood Insert Glass CleaningVoyageur Grand Wood Insert Quick Reference Maintenance Guide Start Fire Problems Possible Cause Solution Troubleshooting GuideGlass Replacement Service Parts ReplacementSnap Disc Replacement Contd Snap Disc ReplacementShock Risk Voyageur Grand Wood Insert Blower ReplacementBaffle & Ceramic Blanket Removal Voyageur Grand Wood Insert Door Handle Assembly51mm. Figure Voyageur Grand Wood Insert Tube Channel Assembly Replacement Getting Started Design and Installation ConsiderationsDraft Voyageur Grand Wood Insert Negative Pressure Chimney Termination Requirements Voyageur Grand Wood Insert Locating Your Stove & ChimneyVoyageur Grand Wood Insert Rule Inspect Appliance and Components Voyageur Grand Wood Insert Tools And Supplies NeededPre-Burn Check List Appliance Dimensions Dimensions and ClearancesWall Clear of Ashes Thermal Resistance R value Thermal Conductivity k valueConverting k to R Converting R to kVenting Systems Chimney SystemsInspections Larger ChimneysVoyageur Grand Wood Insert Masonry Chimney Cont’d Prefabricated Metal Chimney Voyageur Grand Wood Insert Metal Heat Circulating MasonryAltering the Fireplace Voyageur Grand Wood Insert Securing Chimney ComponentsFactory-Built Sold Fuel Fireplace Chimney Height / Rise and Run Items Needed for Installation not supplied Outside Air Kit InstallationOption One Outside Air Installation Instructions Option Two Outside Air Installation InstructionsFlue Adapter Vertical Leveling LegsDegree Standard Surround & Trim Kit Installation 42.1 Voyageur Grand Wood Insert Standard Surround & Cast Trim KitVoyageur Grand Wood Insert All Cast Surround Kit Blower Cord Installation on Left SidePlacement Slot Blower Access Assembly White Wire Mobile Home Installation Part number list on following Service PartsCast Iron Wood Insert Large Stocked #10 Brick AssemblyAt Depot #7 Baffle Protection ChannelDescription Comments Part Number #13 Door Assembly#14 Access Assembly #17 Control Asembly Assemblies #25 & 26 SurroundDate of Service Performed By Description of Service Voyageur Grand Wood Insert Service And Maintenance LogVoyageur Grand Wood Insert Service And Maintenance Log Voyageur Grand Wood Insert Homeowner’s Notes Contact Information