Lochinvar 502, 2072 Location, Hydronic systems anti-freeze, Outdoor pool heater installation

Page 10

Installation & Operation Manual

1 Determine unit location

Anytime the inlet temperature drops below 45°F, the control turns on the pump contact. If the inlet temperature is below 37°F, and the unit is in the ON Mode, the first stage will fire.

Location

Locate indoor pool heaters in a room having a temperature safely above freezing [32°F (0°C)].

￿CAUTION

A mechanical room operating under a negative draft pressure may experience a down draft in the flue of a pool heater when it is not firing. The cold outside air pulled down the flue may freeze a heat exchanger. This condition must be corrected to provide adequate freeze protection.

Figure 1-2_Outside Combustion Air - Single Opening

Two Openings

The combustion air opening must have a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm2 per kW). You

Hydronic systems anti-freeze

Freeze protection for a pool heater using an indirect coil can be provided by using hydronic system antifreeze. Follow the appliance manufacturers instructions. Do not use undiluted or automotive type antifreeze (see page 40).

Outdoor pool heater installation

A snow screen should be installed to prevent snow and ice accumulation around the unit or its venting system.

Combustion and ventilation air

Provisions for combustion and ventilation air must be in accordance with Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA-B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.

Provide properly-sized openings to the equipment room to assure adequate combustion air and proper ventilation when the unit is installed with conventional venting or sidewall venting.

Combustion air options

must locate this opening within 12" (30 cm) of the bottom of the enclosure (see FIG. 1-3).

The ventilation air opening must have a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm2 per kW). You must locate this opening within 12" (30 cm) of the top of the enclosure.

Figure 1-3_Outside Combustion Air - Two Openings

2. Outside Combustion Air, Using Ducts

You can direct outside combustion air to this unit using two air ducts to deliver the air to the mechanical room (see FIG. 1-5).

Each of the two openings must have a minimum free area of one square inch per 2000 Btu input (11cm2 per kW).

3. Combustion Air from Interior Space

￿CAUTION

Under no circumstances should the equipment room ever be under a negative pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the unit.

You can direct combustion air to this unit using air from an adjoining interior space. You must provide two openings from the mechanical room to the adjoining room (see FIG. 1-4).

Each of the two openings must have a net free area of one square inch per 1000 Btu input (22cm2 per kW), but not less than 100 square inches (645cm2).

This unit has four combustion air options.

1. Outside Combustion Air, No Ducts

You can direct outside combustion air to this unit using either one or two permanent openings.

One Opening

The opening must have a minimum free area of one square inch per 3000 Btu input (7 cm2 per kW). You must locate this opening within 12" (30 cm) of the top of the enclosure (see FIG. 1-2).

10

Figure 1-4_Combustion Air from Interior Space

Image 10
Contents Installation & Operation Manual Models 502 Save this manual for future referenceContents Special instructions Please read before proceedingRemoval of Combustion Chamber Lining or Base Panels Safety information Owner warningCopper-fin2- How it works Copper-fin2- How it works Copper-fin2- How it works Specifications RatingsIndoor clearances from combustible construction Determine unit locationLocation of unit Freeze protectionHydronic systems anti-freeze Outdoor pool heater installationLocation Combustion and ventilation airOutside Combustion Air Using Direct Venting Minimum Recommended Combustion AIR Supply to Equipment RoomExhaust fans Combustion air filterCAT IV Flue pipe materials VentingIdentify your appliance’s vent system CAT I Negative pressure non-condensingVent system options Draft VentingVenting support General informationBarometric damper location Flue outlet piping Conventional negative draft venting seeNegative draft Common Venting SystemsVertical vent termination clearances and location Masonry chimney installationsInspection of a masonry chimney 1Vent Termination from Peaked Roof 10 ft. or Less From Ridge Length of air inlet pipe Vertical DirectAire venting seeCombustion air inlet piping Sidewall air inletCombined air inlet points Vertical Rooftop Air InletClearances Venting of flue products Directaire Kits Model Horizontal KIT Vertical KITSidewall venting termination Sidewall venting seeSidewall with fan Sidewall vent termination clearances and locationDrain tee installation Sidewall venting without fanModels 502 Horizontal DirectAire venting Powered Venting see Venting of flue productsFlue outlet piping Direct venting seeVertical DV venting termination Horizontal Vent Termination Clearances and Location Masonry chimney installationHorizontal DV venting termination Combustion air inlet pipingLength of air inlet pipe Connecting the air inlet pipe to the unitAir inlet piping materials Sealing PVC, CPVC, ABS, dryer vent, and flex duct vent pipeHorizontal combustion air inlet clearances Multiple sidewall direct vent installationsVertical and sidewall combustion air inlet Vertical Combustion Air Inlet ClearancesOutdoor vent/air inlet location Outdoor installation seeOutdoor vent cap kit Gas connection Connecting to gas supplyGas connections Gas pressure testGas train and controls Suggested GAS Pipe Size for Single Unit Installations ModelCombination gas valves Venting of combination gas valvesGAS Piping Size Chart Checking gas supply pressure502 752 Models Water connectionsCirculating pump 992 1442 ModelsMinimum Pump Performance Heat exchangerInitial set-up of maximum water flow Auxiliary Mixed Water Limit Control3Heater Within 15 feet of Pool Piping 6Cascaded Heaters Beyond 15 feet of Pool Piping Pool Return Sensor Location MIN Primary Pumped Automatic Bypass Automatic bypass valve cover installationOutdoor operation 3-way valve cover Pump purge pre-running delay Water flow switchPump purge delay Relief valveRemote Wire Connection Way automatic bypass valve wiringWay Automatic Bypass Valve Wiring Electrical connectionsLine voltage connections Installation must comply withPool heater operating control module AMP Draw DataPool supply/limit sensor 4-wire Louver proving switchPool return sensor 2-wire Low voltage connectionsAlarm contacts Wiring of the cascadeStarting the filter system Pre-start checklistStartup Check for gas leaksPlacing the pool heater in operation Check thermostat circuitsCheck vent and air piping Start the pool heater2Operating Instructions Configuration of the cascade Set clockOperating information GeneralPool heater temperature regulation Cascade DAY Switching on SequenceSequence of the cascade Sequence of operation MENU/EXIT Display Screen ENTER/RESET Updown Copper-fin2control moduleUser Access modesInstaller To save parameters and exit programmingStatus display screens Sysrtn Shorted Unit Pump DelaySysrtn Open STG DemandService technician Maintenance Maintenance and annual startupOwner maintenance Inspect appliance area MaintenanceAddress reported problems Inspect appliance interiorCheck relief valve Inspect/replace hot surface igniter Check all wiringCheck control settings Ignition system checkoutPerform start-up and checks Check burner flame Inspect and clean burnerCheck flue gas passageways Review with owner Oiled bearing circulatorsConnection diagram Digital HarnessController Ladder diagram LOW VoltageRuntime Contacts 2BOARDCONNECTION Outdoor S5SENSOR POOL2ND Page
Related manuals
Manual 44 pages 17.92 Kb Manual 16 pages 36.89 Kb

2072, 502 specifications

Lochinvar 2072,502 is an innovative and robust water-heating solution tailored for residential and commercial applications. This model represents a significant advancement in energy efficiency and performance, catering to the dynamic heating requirements of modern buildings.

One of the standout features of Lochinvar 2072,502 is its advanced thermal efficiency. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, the unit delivers exceptional heat output while minimizing energy consumption. This not only reduces utility bills for homeowners and businesses but also supports sustainability efforts by decreasing carbon footprints.

The Lochinvar 2072,502 incorporates cutting-edge technologies that set it apart in the market. It is equipped with advanced control systems that allow users to precisely manage heating outputs, ensuring optimal comfort while conserving energy. The user-friendly digital display provides real-time data, allowing for efficient monitoring and control.

Another significant characteristic of the Lochinvar 2072,502 is its robust stainless-steel construction. This feature enhances the unit's durability and longevity, ensuring reliable performance even in challenging conditions. The high-quality materials also contribute to maintaining consistent water temperatures, which is essential for both residential and commercial heating needs.

The Lochinvar 2072,502 operates silently, making it ideal for installations in areas where noise is a concern. Its compact design allows for flexible installation options, fitting seamlessly into various spaces, whether it’s a utility room, basement, or outdoor area.

Furthermore, the unit supports multiple venting options, accommodating different building architectures and layouts. This versatility makes it an ideal choice for new builds and retrofitting existing systems.

Maintenance is streamlined with the Lochinvar 2072,502, as it features a self-diagnostics system that simplifies troubleshooting. Regular service check-ups are made easier with accessible components, allowing technicians to perform maintenance tasks efficiently.

In summary, the Lochinvar 2072,502 stands out for its high efficiency, advanced technology, durability, and flexible installation options. It is an ideal choice for those seeking a reliable and technologically advanced water-heating solution that meets the challenges of contemporary heating demands while promoting energy savings and environmental responsibility.